Configuration
8.3 Device configuration and configuration parameters in the TIA Portal
Configuration parameters POM4220 Highend
Description
Control type
(setting once per POM)
Connection type
(setting once per POM)
Phase LX1
(setting once per POM)
Phase LX3
(setting once per POM)
Soft start for each channel switch-on
operation
(setting once per POM)
Enable output control
(setting once per POM)
Enable fault current monitoring
(setting once per POM)
Threshold for fault current monitoring
Response to errors
(setting per channel)
Parallel switching of loads
(setting per channel)
Total power rating
(setting per channel)
Max. permitted deviation from total
power
(setting per channel)
With the exception of the parameter "Response in the event of fault", all other parameter settings
1)
are irrelevant for this type of connection.
The parameters "Phase LX1" and "Phase LX3" are only relevant for connections between phase
2)
and neutral conductor.
110
2)
2)
Value range
Half-wave control (default)
•
Half-wave control with soft start version 1
•
Half-wave control with soft start version 2
•
Half-wave control with adaptive soft start
•
Phase control
•
Phase control with soft start version 1
•
Phase control with soft start version 2
•
Phase angle control with adaptive soft start
•
Connection between phase and N-conductor
•
Connection between phase and phase
•
2-pin connection between phase and neutral conductor
•
2-pin connection between phase and phase
•
Economy circuit
•
1)
Connected (default)
•
Not connected
•
Connected (default)
•
Not connected
•
No (default)
•
Yes
•
No (default)
•
Yes
•
No (default)
•
Yes
•
400 to 2000 mA
•
Channel substitute value 0 (default)
•
Channel value is retained
•
No (default)
•
Yes
•
400 ... 9600 W
•
50 ... 2000 W
•
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006