Configuration parameters POM4320 Highend
Description
Control type
(setting once per POM)
Connection type
(setting once per POM)
Soft start for each channel switch-on
operation
(setting once per POM)
Enable output control
(setting once per POM)
Parallel connection of channels
Enable fault current monitoring
(setting once per POM)
Threshold for fault current monitoring
Response to faults
(setting per channel)
Parallel connection of loads
(setting per channel)
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
8.3 Device/hardware configuration in the TIA Portal
Value range
Half-wave control (default)
•
Half-wave control with soft start variant 1
•
Half-wave control with soft start variant 2
•
Half-wave control with soft start variant 3
•
Half-wave control with adaptive soft start
•
Phase control
•
Phase control with soft start variant 1
•
Phase control with soft start variant 2
•
Phase control with soft start variant 3
•
Phase control with adaptive soft start
•
Connection between phase and phase (internal fuse)
•
(default)
Connection between phase and phase (external fuse)
•
Connection between phase and neutral conductor
•
2-pin connection between phase and phase
•
Connection between phase and phase (closed delta)
•
No (default)
•
Yes
•
No (default)
•
Yes
•
No (default)
•
All channels
•
One channel (1-2)
•
One channel (3-4)
•
One channel (5-6)
•
Two channels (1-2, 3-4)
•
Two channels (1-2, 5-6)
•
Two channels (3-4, 5-6)
•
No (default)
•
Yes
•
400 mA to 2,000 mA
•
Channel substitute value 0 (default)
•
Channel value retained
•
No (default)
•
Yes
•
Configuring/Programming
87