Article number
Errors/accuracies
•
•
•
Connection method
•
Interfaces
Interfaces/bus type
Interrupts/diagnostics/status information
Number of status displays
LED status display
Integrated Functions
Measuring functions
•
Measuring inputs for current
Potential separation
between the channels
Isolation
Overvoltage category
Degree of pollution
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
Measuring accuracy
Temperature drift per °C, typ.
Temperature offset per K, max.
Design of electrical connection for tempera-
ture sensors
–
Connectable conductor cross-sections
for AWG cables
–
Connectable conductor cross-sections,
solid
–
Connectable conductor cross-sections
with wire end processing
Current measurement
–
Current measurement range, min.
–
Current measurement range, max.
–
Relative measuring accuracy current
–
Design of electrical connection at the
measuring inputs for current
–
Connectable conductor cross-sections,
solid
–
Connectable conductor cross-sections,
finely stranded with wire end pro-
cessing
–
Connectable conductor cross-sections
for AWG cables
Technical specifications
13.4 Technical specifications for I/O module
6BK1900-0AA00-0AA0
±1 K
0.05 %/°C
0.1 K/K
1x 8 pole connector with spring-loaded connec-
tion
1x (24 ... 16)
1x (0.2 ... 1.5 mm²)
1x (0.25 ... 1.5 mm²)
system interface
2
LED green = Ready, LED red = Error display
Yes
0 mA
20 mA
0.5 %
1x 8 pole connector with spring-loaded connec-
tion
1x (0.2 ... 1.5 mm²)
1x (0.25 ... 1.5 mm²)
1x (24 ... 16)
No
III
2
189