Communications
The information provided in the section "Communication" refers to Siemens SIMATIC S7
controllers, but this also applies to other controllers with PROFINET/PROFIBUS due to the
standardized PROFINET/PROFIBUS communication.
10.1
Cyclic data exchange
10.1.1
Cyclic output data
Cyclic data exchange between the heating control system and the S7 controller takes place
via the process and /I/O address area of the CPU. The cyclic data can be addressed in the
S7 controller through the process image or I/O commands.
Cyclic output data for CIM
Byte
0
1
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
Control bit
Meaning
0
Heater
0: Switch off heating
1: Switch on heating
1
Operating mode
0: Select "Production" mode
1: Select "Standby" mode
2
Line voltage compensation
0: Switch off
1: Switch on
3
0 (not in use)
4
0 (not in use)
5
0 (not in use)
6
0 (not in use)
7
0 (not in use)
–
0 (not in use)