Special features of POM4320 Highend
Parallel connection of channels
Error
code
5106
2-pin connection between phase and phase
Error
code
5104
5105
5107
Connection between phase and phase (closed delta)
Error
code
5105
5107
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
Meaning
K1, K3 or K5
One or both incoming fuses
are defective
K2, K4 or K6
–
Meaning
Channel 1, 4 and 6 Both Triacs have broken
down
Channel 3, 5 and 2 Exactly one Triac has broken
down
–
–
Channel 1, 4 and 6 •
External fault
Fuse F1 ... F6 is defec-
•
tive
Triac 1 ... 6 has high
•
resistance
Channel 3, 5 and 2 –
Meaning
Channel 1, 3 and 5
At least one of the channel
fuses is defective
Channel 2, 4 and 6
Channel 1, 3 and 5
At least one of the loads
connected to the channels is
Channel 2, 4 and 6
defective
10.3 Transfer of diagnostic alarms to the controller
Description
Channel fault:
Incoming fuse defective
–
Description
The error message is generated via
channels 1, 4 and 6.
The error message is generated via
channels 3, 5 and 2.
–
The error message is generated via
channels 1, 4 and 6.
No distinction is possible between an
external fault and a fuse fault.
Therefore, the error code 5107 in-
cludes the following errors:
Channel fault "Triac has high
•
resistance" and
"outgoing fuse defective"
Channel fault "external fault"
•
See section Fault reporting
through diagnostics data
(Page 146)
–
Description
A distinction which fuse is defective is
not possible
A distinction which of the loads is
defective is not possible