Servicing and maintenance
12.6 Replacing the Central Interface Module (CIM)
12.6
Replacing the Central Interface Module (CIM)
Requirements
● The AC power supply is disconnected from the supply at the mounting location of the
device and secured against switching on again.
● The 24 V DC supply voltage must be disconnected.
Tool
You will need a Torx T10 screwdriver.
Removing the CIM
Figure 12-5
Procedure for removing the CIM
160
Removing the CIM
1
Remove all connectors from the CIM.
•
Detach the connector from the system interface to the POM.
•
2
Remove the four screws
①
and detach the CIM from the POM
Operating Instructions, 10/2019, A5E35452705A/005
②
.
SIPLUS HCS4300 PROFINET/PROFIBUS DP