F814
Communications Frequency 2
Program  Communication Settings
This parameter is used to set the gain and bias of the Communications Speed 2
speed control input.
See
F811
for more information on this setting.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Baud Rate (RS485 4-Wire)
Program  Communication Settings
This parameter sets the RS485 baud rate.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Settings:
0 — 9600 bps
1 — 19200 bps
2 — 38400 bps
RS485 Send Wait Time (RS485 4-Wire)
Program  Communication Settings
This parameter sets the RS485 response delay time.
Changes made to this parameter require that the power be cycled (off then on) for
the changes to take effect.
Q9 ASD Installation and Operation Manual
Direct Access Number — F814
Parameter Type — Numerical
Factory Default — 60.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F820
Parameter Type — Selection List
Factory Default — 19200
Changeable During Run — Yes
Direct Access Number — F825
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 2.00
Units — Seconds
F825