FM Output Gradient Characteristic
Program  AM/FM
This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+) to
the input signal.
See
F005
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
FM Bias Adjustment
Program  AM/FM
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the FM terminal.
Set the assigned function of
proper operation.
See
F005
for more information on this setting.
FM Output Filtering
No Path — Direct Access Only
Analog filtering is applied after the analog reference signal is converted to a
digital signal. The type of filtering used is Rolling Average over time.
Select the sampling rate from the list below.
Settings:
0 — None (1 ms)
1 — Small (8 ms)
2 — Medium (16 ms)
3 — Large (32 ms)
4 — Huge (64 ms)
An increased value here may eliminate false responses to electrical noise with no
loss in bandwidth because the value used by the ASD is the average value of a
number of samples.
See
F005
for more information on this setting.
AM Output Gradient Characteristic
Program  AM/FM
This parameter sets the output response polarity of the AM output terminal.
The AM output terminal response may be set to respond inversely (-) or directly
(+) to the input signal.
See
F670
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
144
F005
to zero and then set this parameter to zero for
Direct Access Number — F682
Parameter Type — Selection List
Factory Default — Plus (Positive
Gradient)
Changeable During Run — Yes
Direct Access Number — F683
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — -10.0
Maximum — +100.0
Units — %
Direct Access Number — F684
Parameter Type — Selection List
Factory Default — None (1 ms)
Changeable During Run — Yes
Direct Access Number — F685
Parameter Type — Selection List
Factory Default — Plus (Positive
Gradient)
Changeable During Run — Yes
Q9 ASD Installation and Operation Manual