F503
Acc/Dec Pattern 2
Program  Fundamental 2
This parameter enables a user-selected preprogrammed output profile that controls
the acceleration and deceleration patterns for the Accel/Decel 2 parameter. See
F502
for more information on this parameter.
Settings:
0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2
Panel Acc/Dec Selection
Program  Panel Control
Two Accel/Decel profiles may be set up and run individually.
Accel/Decel Time 1 or 2 may be selected using this parameter setting. The system
may also be configured to switch between the number 1 and the number 2 profiles
under user-set conditions.
Switching may be accomplished manually via a properly configured discrete input
terminal or automatically via a threshold frequency setting.
This parameter is used to manually select one of the configured accel/decel
profiles to be used.
Settings:
1 — Acc/Dec 1
2 — Acc/Dec 2
Each Accel/Decel selection is comprised of an Acceleration Time, Deceleration
Time, and a Pattern selection.
Accel/Decel 1 includes a Switching Frequency setting (F505). The Switching
Frequency is used as a threshold frequency that, once reached (during accel or
decel), the ASD switches to the other profile.
Acc/Dec 1 is set up using parameters
(Pattern), and
F505
(Switching Frequency).
Acc/Dec 2 is set up using parameters
F503
(Pattern).
To switch using a discrete input terminal, assign the function A/D 1/2 to an
unused discrete input terminal. Activating or deactivating the A/D 1/2 terminal
toggles to and from the Accel/Decel profiles 1 and 2 and will override the setting
of this parameter.
Figure 27
shows the setup requirements and the resulting output frequency
response when using Switching Frequency settings to control the Acc/Dec
profile of the ASD output.
Accel/Decel Switching Frequency 1
Program  Fundamental 2
This parameter sets the frequency at which the acceleration/deceleration control is
switched from the Accel 1 profile to the Accel 2 profile or from the Decel 2 to the
Decel 1 during a multiple-acceleration/deceleration profile configuration.
See
F504
for more information on this parameter.
Q9 ASD Installation and Operation Manual
F009
(Acc Time),
F010
(Dec Time),
F500
(Acc Time),
F501
(Dec Time), and
Direct Access Number — F503
Parameter Type — Selection List
Factory Default — Linear
Changeable During Run — Yes
Direct Access Number — F504
Parameter Type — Selection List
Factory Default — Acc/Dec 1
Changeable During Run — Yes.
Figure 27. Using Acc/Dec Switching.
1 — Accel time 1
(F009
2 — Accel time 2
(F500
3 — Decel time 2
(F501
4 — Decel time 1
(F010
F505
— Frequency threshold setting at
F502
which the 1-to-2 and the 3-to-4 switch
Direct Access Number — F505
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F505
setting)
setting)
setting)
setting)
129