7.3

Standby Battery Calculation

Use the following formula to calculate standby battery capacity for 24 hr of standby power and 4 to 30 minutes
of alarm power:
(Total B _____ x 24 hr) + (Total C _____ x Y hr*) + 10% reserve = Total battery Ah required
* Y hr =
For UL-approved residential applications (household), Y = 0.067 (4 minutes)
-
For UL-approved commercial applications, Y = 0.25 (15 minutes)
-
For ULC-approved commercial applications, Y = 0.50 (30 minutes)
-
If the Column C total exceeds 1.4 A, use an external power supply.
Model Number
Quantity
Used
Control Panel
Control Center
Wireless Hub
(IWT-WSN-N1-86)
DX2010
Sounders Connected to PO 4
D118 8 Ω Speaker
Ratings of other devices in system that are not shown above
Bosch Security Systems, Inc. | 5/07 | F01U025147-01
Easy Series (ICP-EZM2) | Installer Guide | 7.0 Reference Materials
A
AC Power On
Normal Current
Each
Total
Unit
(mA)
(mA)
85
x 1
=
85
110
x Qty
=
30
x 1
=
30
35
x Qty
=
0
x Qty
=
0
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
Total
=
A
B
AC Power Off
Minimum Current
Each
Total
Unit
(mA)
(mA)
85
x 1
=
85
110
x Qty
=
30
x 1
=
30
35
x Qty
=
0
x Qty
=
0
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
Total
=
B
C
In Alarm
Maximum Current
Each
Total
Unit
(mA)
(mA)
160
x 1
=
160
165
x Qty
=
30
x 1
=
30
35
x Qty
=
330
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
x Qty
=
Total
=
C