Same phase sequence in the precharging and main circuits
It is absolutely imperative that the precharging and main circuits have the same phase
sequence. If this is not the case, during the brief overlap period, where both contactors are
simultaneously closed, the precharging resistors will be overloaded and could be
destroyed.
3.3.3.3

Line/load connection

Table 3- 18
Line/load connection of the Smart Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
PE1, PE2
) Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
CAUTION
Technical specifications
Voltage:
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
Frequency: 47 ... 63 Hz
Connecting thread:
Frame size GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Voltage:
500 ... 630 V DC
650 ... 900 V DC
Connections:
Frame size GX: Threaded bolts M6 / 6 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HX / JX: Connection for connection clip
Voltage:
500 ... 630 V DC
650 ... 900 V DC
Connections:
Frame size GX: Thread M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Frame sizes HX / JX: d = 12 mm (M12/50 Nm) flat connector for busbar
Connecting thread:
Frame size GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 /
DIN 46235
1)
Line Modules
3.3 Smart Line Modules
1)
1)
127