Siemens SINAMICS S120 Manual page 116

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line Modules
3.2 Basic Line Modules
Order number
Dimensions
- Width
- Height
- Depth
Frame size
Weight
Recommended fuse
2)
- Number (connected in parallel)
- Rated current
- Frame size acc. to IEC 60269
Minimum short-circuit current
The specified power loss is the maximum value at 100% capacity utilization. The value in normal operation is lower.
1)
To achieve a UL-approved system, it is absolutely essential to use the fuse types specified in the table.
2)
Current required for reliable triggering of the protective devices.
3)
114
6SL3330–
mm
mm
mm
kg
A
3)
1TG33–0AA3
1TG34–3AA3
310
310
1164
1164
352
352
FB
FB
96
96
3NE1230-2
3NE1333-2
1
1
315
450
2
2
3000
4400
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
1TG36–8AA3
1TG41–1AA3
310
310
1164
1653
352
550
FB
GB
96
214
3NE1436-2
3NE1334-2
1
2
630
500
3
3
8000
10400
Chassis power units

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents