Table 6- 26
Technical data of the dV/dt filter plus voltage peak limiter, 3 AC 500 ... 690 V, Part 1
Order number
Suitable for Motor Module
Type rating of the Motor
Module
I
thmax
Degree of protection
dV/dt reactor
Power loss
- At 50 Hz
- At 60 Hz
- At 150 Hz
Connections
- To the Motor Module
- Load
- PE
Max. permissible cable
length between dV/dt
reactor and motor
Dimensions
Width
Height
Depth
Weight, approx.
Voltage peak limiter
Power loss
- At 50 Hz
- At 60 Hz
- At 150 Hz
Connections
- To the dV/dt reactor
- DC
- PE
Dimensions
Width
Height
Depth
Weight, approx.
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
6SL3000-
2DH31-0AA0
6SL3320-
1TG28-5AAx
kW
75
A
100
IP00
kW
0.49
kW
0.508
kW
0.541
M10
M10
M6
m
mm
350
mm
320
mm
227
kg
48
kW
0.016
kW
0.015
kW
0.013
M8
M8
M8
mm
263
mm
265
mm
188
kg
6
Motor-side power components
6.3 dv/dt filter plus Voltage Peak Limiter
2DH31-0AA0
2DH31-5AA0
1TG31-0AAx
1TG31-2AAx
90
100
IP00
IP00
0.49
0.389
0.508
0.408
0.541
0.436
M10
M10
M6
300 (shielded)
450 (unshielded)
350
320
227
48
0.016
0.020
0.015
0.019
0.013
0.018
M8
M8
M8
263
265
188
6
2DH31-5AA0
1TG31-5AAx
110
132
150
150
IP00
0.389
0.408
0.436
M10
M10
M10
M10
M6
M6
350
350
320
320
227
227
50
50
0.020
0.019
0.018
M8
M8
M8
M8
M8
M8
263
263
265
265
188
188
6
6