Siemens SINAMICS S120 Manual page 338

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Maintenance and Servicing
8.4 Replacing components
Preparatory steps
● Disconnect the drive line-up from the power supply
● Allow unimpeded access to the power block
● Remove the protective cover
Removal
The removal steps are numbered in accordance with the numbers in the diagram.
1. Remove the busbar (twelve screws).
2. Unscrew the connection to the DC link (eight nuts).
3. Remove the retaining screw at the top (one screw).
4. Remove the retaining screws at the bottom (two screws).
5. Disconnect the plug-in connections for the fiber-optic cables and signal cables (two
6. Remove the connection for the current transformer and associated PE connection (two
7. Unscrew the two retaining screws for the fan and attach the equipment for assembling
You can now remove the power block.
Caution when removing
The power block weighs approx. 86 kg!
When removing the power block, ensure that you do not damage any signal cables.
The second plug connection for the fiber optic cables cannot be disconnected until the
power block has been pulled out slightly (see Step 5).
336
connectors).
The second plug connection for the fiber optic cables cannot be disconnected until the
power block has been pulled out slightly.
connectors).
the power block at this position.
CAUTION
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Chassis power units

Hide quick links: