Adjusting the fan voltage (-T10)
The power supply for the device fans (1 AC 230 V) in the Basic Line Module (-T10) is taken
from the line supply using transformers. The installation position of the transformers is
indicated in the interface descriptions.
The transformers are fitted with primary taps so that they can be fine-tuned to the line supply
voltage.
If necessary, the connection fitted in the factory, shown with a dashed line, must be
reconnected to the actual line voltage.
Figure 3-10
The supply voltage assignments for making the appropriate setting on the fan transformer
are indicated in the following tables (factory presetting: 480 V / 0 V or 690 V / 0 V).
Note
With the 3 AC 500 V to 690 V fan transformer, a jumper is inserted between the "600 V"
terminal and "CON" terminal. The "600 V" and "CON" terminals are reserved for internal use.
NOTICE
Consequences of incorrect voltage setting
If the terminals are not reconnected to the actual line voltage:
• The required cooling level will not be provided (risk of overheating).
• The fan fuses may blow (overload).
Table 3- 10
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Setting terminals for the fan transformers (3 AC 380 to 480 V / 3 AC 500 to 690 V
Line voltage assignment for the setting at the fan transformer (3 AC 380 ... 480 V)
Line voltage
380 V ± 10%
400 V ± 10%
440 V ± 10%
480 V ± 10%
Tap at the fan transformer (-T10)
380 V
400 V
440 V
480 V
Line Modules
3.2 Basic Line Modules
105