8.5 Meaning of the LED

Table 8-8
Suggestions for terminals and cable lugs which can be used for tapping line voltage for the VSM10
Conductor cross-section
Up to 6 mm
2
6 mm
to 16 mm
2
2
16 mm
to 50 mm
2
2
> 50 mm
2
8.5
Meaning of the LED
Table 8-9
Meanings of the LEDs on the Voltage Sensing Module VSM10
LED
Color
READY
Green
Orange
Red
Green/red
Green/
orange
or
Red/
orange
Cause and rectification of faults
Further information about the cause and rectification of faults is available in the SINAMICS S120
Function Manual "Drive Functions".
222
Connection via
Direct connection possible
ST16-TWIN terminal blocks,
if required with a reducing jumper and ST4-TWIN or
ST2.5-TWIN
(Phoenix Contact company)
AGK10 UKH tap-off terminals with UKH terminals
(Phoenix Contact)
Ring cable lug without insulation (Page 323) 8 mm/
2.5 mm
2
Intermediate high-current connector,
type UHV (Phoenix Contact) and ring cable lug
without insulation (Page 323) 8 mm/2.5 mm
Status
Description, cause
Off
The electronics power supply is missing or outside the permis‐
sible tolerance range.
Continu‐
The component is ready for operation. Cyclic DRIVE-CLiQ com‐
ous light
munication is taking place.
Continu‐
DRIVE-CLiQ communication is being established.
ous light
Continu‐
This component has at least one fault.
ous light
Note:
LED is controlled irrespective of the corresponding messages
being reconfigured.
Flashing
Firmware is being downloaded.
light 0.5
Hz
Flashing
Firmware download is complete. The system waits for POWER
light 2 Hz
ON.
Flashing
Detection of the component via LED is activated (p0144 = 1).
light
Note:
2 Hz
Whether the LED flashes green/orange or red/orange depends
on the status the LED had during activation (setting of param‐
eter p0144 to "1").
For components
Smart Line Modules 5 kW and 10 kW
Active Line Modules 16 kW
Smart Line Modules 16 kW
Active Interface Module 16 kW
Active Line Modules 36 kW and 55 kW
Smart Line Modules 36 kW and 55 kW
Active Interface Module 36 kW and 55 kW
Components with M8 connection bolts
Active Line Modules 55 kW, 80 kW, and
120 kW
Active Interface Module 80 kW and 120 kW
2
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
Remedy
Remove and acknowl‐
edge the fault.
Carry out a POWER ON.