Terminal Modules
6.6 Terminal Module TM54F
6.6.2.2

X500/X501 DRIVE-CLiQ interfaces

Table 6-33
Connector
type
The blanking covers for the DRIVE-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
Note
The maximum DRIVE-CLiQ cable length is 100 m.
6.6.2.3

X514 power supply for digital outputs and sensors

Table 6-34
Type: Spring-loaded terminal 6 (Page 320)
The maximum cable length is 30 m.
Note
The two "+" and "M1" terminals are jumpered in the connector. This ensures that the supply
voltage is looped through.
160
X500/X501 DRIVE-CLiQ interfaces
Pin
Signal name
1
TXP
2
TXN
3
RXP
4
Reserved, do not use
5
Reserved, do not use
6
RXN
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
B
M (0 V)
DRIVE-CLiQ socket
X514: Power supply
Terminal
Designation
+
Power supply (24 V)
+
Power supply (24 V)
M1
Electronics ground (0 V)
M1
Electronics ground (0 V)
Technical data
Transmit data +
Transmit data -
Receive data +
-
-
Receive data -
-
-
Power supply
Electronics ground
Technical data
Voltage: 24 V DC (20.4 ... 28.8 V)
Current consumption: max. 4.0 A
(including DRIVE-CLiQ and digital out‐
puts)
Max. current via jumper in connector:
20 A (15 A according to UL/CSA)
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2