7.4.4

Installation

Ø5,3 (0.21)
Figure 7-7
Installation
1. Place the drilling pattern on the mounting surface. Make sure that the contact surface is bare,
unpainted metal.
2. Drill two holes with Ø 5.3 or M5 threaded holes according to the drilling pattern.
3. Mount the DME20 DRIVE-CLiQ Hub Module External on the contact surface. The tightening
torque is 6.0 Nm (53.1 lbf in).
7.4.5

Technical data

Table 7-9
6SL3055-0AA00-6AB.
Electronics power supply
Voltage
Current (without DRIVE-CLiQ node)
Power loss
Protective ground conductor connection
Weight
Control Units and additional system components
Equipment Manual, 06/2020, 6SL3097-5AH00-0BP2
87,5 (3.44)
99 (3.90)
M5
Contact surface
Mounting dimensions DME20
Technical data of the DME20
7.4 DRIVE-CLiQ Hub Module External DME20
1
Unit
V
DC
A
DC
W
Screwed to the housing M5
kg
Hub Modules
Value
24 (20.4 ... 28.8)
≤0.2
≤4
0.8
211