86/327
Building Technologies
6.3 Direction of rotation of the actuators
The actuators' direction of rotation can be set in the Params & Display ⇓ Actuators
⇓ DirectionRot menu. This enables the direction of rotation to be matched to the
mounting method.
The direction of rotation must be selected before defining the ignition position and
curvepoints. If this is not observed, these points must be deleted before the direction of
rotation is reversed. For that purpose, the DeleteCurves function is offered in the menu
for selecting the direction of rotation.
Select the direction of rotation as standard or reversed.
The standard direction of rotation is anticlockwise when facing the end of the drive
shaft.
Parameter:
1 AirActuator (standard / reversed)
2 GasActuator (standard / reversed)
(and OilActuator, if NumFuelActuators =
1)
3 OilActuator (standard / reversed)
4 AuxActuator (standard / reversed)
5 AuxActuator2 (standard / reversed)
6 AuxActuator3 (standard / reversed)
Basic Documentation LMV5...
6 Fuel-air ratio control (FARC)
LMV51
LMV50
LMV51.3
˜
˜
˜
˜
˜
˜
˜
˜
˜
LMV52
˜
˜
˜
˜
˜
˜
CC1P7550en
22.05.2018