Requirements placed on
sensor and protection
pocket
124/327
Building Technologies
If the internal
temperature limiter
temperature sensor with protection pocket must not exceed 45 seconds.
1
0.63
T
Figure 60: Instant temperature change of test medium to determine the time constant
Legend
Ι M
Temperature of test medium
X a
Output signal of temperature sensor
T
Time constant
Basic Documentation LMV5...
7 Boiler controller / load controller
function is used, the time constant «T» of the
Ι
M
X
a
7550d19E/0502
Time t
CC1P7550en
22.05.2018