Siemens LMV50 Series Manual page 160

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

160/327
Building Technologies
Now, the value can be changed and the respective actuator follows at the rate of the set
ramp speed.
Enter saves the value, Esc discards it.
This way, all stages can be set, one by one.
The following table shows the response of the system when a point is selected.
However, the relevant valve is switched on only when at least the switch-on point is
definitely used (÷ XXXX).
Selected point
Operating point stage 1
Switch-on point stage 2
Switch-off point stage 2
Operating point stage 2
Switch-on point stage 3
Switch-off point stage 3
Operating point stage 3
System response when a point is selected
Basic Documentation LMV5...
8 Display and operating unit AZL5
Response
Remark
Approach of stage 1
Fine adjustment of stage 1
Approach of stage 1
Adjustment of stage 1 off
--
Adjustment of stages 1 and 2 off
Approach of stage 2
Fine adjustment of stage 2
Approach of stage 2
Adjustment of stage 2 off
--
Adjustment of stages 2 and 3 off
Approach of stage 3
Fine adjustment of stage 3
CC1P7550en
22.05.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents