Siemens LMV50 Series Manual page 178

Hide thumbs Also See for LMV50 Series:
Table of Contents

Advertisement

24. Ignition positions
Menu level 1
Menu level 2
Params & Display
RatioControl
178/327
Building Technologies
The burner control proceeds with the startup sequence until the ignition position (phase
36) is reached. There, the burner control stops again for setting the ignition positions of
the actuators.
Menu level 3
OilSettings
To repeatedly verify the ignition positions, the control sequence can be stopped in
interval phase 44 or 52 (interval with ignited flame on completion of the respective
safety time).
When the program stop is deactivated, the burner proceeds with its program until normal
operation is reached (phase 60).
If the switching points of the burner stages have not yet been defined, the ignition
positions of the actuators are used as the first stage for the moment.
Basic Documentation LMV5...
9 Commissioning instructions for the LMV5
Menu level 4
Menu level 5
SpecialPositions
IgnitionPos
Menu level 6
IgnitionPosOil
IgnitionPosAir
IgnitionPosAux1
IgnitionPosAux2
Only LMV52
IgnitionPosAux3
LMV50/LMV51.3/
IgnitionPosVSD
LMV52
CC1P7550en
22.05.2018

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents