9.2 nV-Tool Error

Code
Contents
0x0000
Normal
0x0002
Hardware
is
abnormal
(time-out
error
etc.)
0x0004
Access refusal
(operation mode
is injustice)
0x0101
Command code
error
0x0102
Text format error
(size)
0x0103
Text parameter
error
Table 9-2 nV-Tool error(1)
Normal
Target node has seceded from the network though the command for that node was
received from nV-Tool.
FL654A is set to AUTO/CONF specification, the following command was received from
nV-Tool.
Writing of Cyclic transmission specification, Message transmission specification, Token
watch time, Minimum permissible frame interval, Talker area, Node name, I/O module
configuration information setting, I/O data allocation Information setting, Clear Error
counter, Clear Memory, Read out Operation history log, Error reset command, RUN
command, HALT command,
FL654A is set to TOOL specification, FL654A is I/O run mode, the following command was
received from nV-Tool.
Writing of Cyclic transmission specification, Message transmission specification, Token
watch time, Minimum permissible frame interval, Talker area, Node name, I/O module
configuration information setting, I/O data allocation Information setting.
FL654A is set to TOOL specification, FL654A is Down mode, the following command was
received from nV-Tool.
Writing of Cyclic transmission specification, Message transmission specification, Token
watch time, Minimum permissible frame interval, Talker area, Node name, I/O module
configuration information setting, I/O data allocation Information setting.
"command" of the transmission frame received from nV-Tool is abnormal.
"Address_data_type" or "Address_data_length" in the transmission frame received from
nV-Tool is abnormal.
"MsgLen" in the transmission frame received from nV-Tool doesn't agree with the length of
the transmission message of a pertinent command.
"Data_type" or "Data_number" in the transmission frame received from nV-Tool is
abnormal.
Network address part of IP address in the transmission frame received from nV-Tool is
different from the network address of the node.
I/O initialization abnormality
・ I/O configuration is not preserved or it is destroyed.
・ I/O configuration and actual I/O mounting information are different.
・ I/O that cannot support is mounted.
・ Cyclic area allocation of I/O configuration is abnormal.
・ Input / Output execution is neither "execution: 1" nor "non-execution: 0".
・ The head address of talker is not a range of 0 to 8703.
Module parameter abnormality
Cyclic area of I/O configuration beyond the limits of own cyclic taker area.
The value of the cyclic transmission designation write is neither "Cyclic transmission: 1" nor
"Cyclic transmission: 0".
In the message transmission specification write, the value is not "message transmission: 1"
Token watch time beyond the limits of 1to 255
Minimum permissible frame interval beyond the limits of 0 to 50
Unified Controller nv Series FL-net Remote I/O Station Module FL654A User's Manual
Factors
9.2 nV-Tool Error