Toshiba FL654A User Manual page 60

Fl-net remote i/o station module
Table of Contents

Advertisement

Chapter 7 RAS Function
Contents
mode
message
cyclic
LNK
ERR
PVERR
GDLNK
DPADR
TEST
When FL654A is down mode, the down code is displayed under "mode".
7
0x0000
NMI occurrence
0x0010
External WDT error
0x0020
Bus stall
0x0030
Occurrence of general
exception
0x0160
ROM area check failure
0x0260
RAM area check failure
0x0261
Program area check failure
0x0600
Detection of a duplicated
node number
0x0601
FL-network sign-up failure
0x0700
Node number setting error
0x0800
Protocol version
disagreement
0x0900
Format error
0x0A01
Ethernet setting failure
0x0A03
I/O configuration information
setting failure
0x0A04
I/O configuration information
abnormality
0x0A05
I/O configuration information
not saved
0x0A06
Failure to save I/O
configuration information
0x0A07
Common memory area
allocation error
44
6F8C1625
Status
The state of the FL654A is displayed.
RUN ... Join in the network, and the I/O operation is executed
STBY ... Join in the network, and the I/O operation is stopped
DOWN ... Down mode
Display of enable / disable for message data transmission
Display of enable / disable for cyclic data transmission
Display of join in (ON) / leave from (OFF) the network
Display of abnormality (ON) / normality (OFF) of the parameter
Display of the protocol version disagreement
Detection (ON) / No detection (OFF)
Display of the result of the transmission line link test
Normality (ON) / Abnormality (OFF)
Display of the detection of duplicated node number
Detected (ON) / Not detected (OFF)
Always turning off
Down code
Table 7-3 Node status
Contents
Table 7-4 Down code
NMI occurred due to unknown cause
NMI occurred due to an external WDT.
NMI occurred due to bus stall.
Occurrence of general exception
Error was detected by FROM's BCC check at initialization.
Error was detected by RAM check at initialization.
Error was detected by BCC check on the SRAM program area at
initialization or during operation.
A duplicated node number was detected at sign-up to the network.
An FL network sign-up failure was detected.
The node address switch has been incorrectly set. (0x00, 0xFF)
Disagreement of the FA link protocol version was detected.
An FA link protocol parameter was detected to be wrong. (Detection of
test operation only)
Ethernet setting (operation setting switch bits 1 and 2) was detected to
be faulty.
Setting of I/O configuration information (operation setting switch bits 3
and/or 4) was detected to be incorrect.
The information saved in FRAM does not match the actual mounting
status, I/O module status, type, number of I/O points. Or, the status is an
abnormal value.
I/O configuration information is not stored in FRAM
I/O configuration information can not be stored in FRAM
I/O can not be allocated to common memory area
Description