7.2.1.2 Termination
For point-to-point connections, always activate the termination. For
multi-point connections, only activate the termination at the cable end.

Fig. 7-8: Block diagram termination RS422 / RS485

Designation
Value
R1, R3
510 Ohm
R2
150 Ohm
R4
120 Ohm
Fig. 7-9: Resistance values termination RS422 / RS485
The switch positions for ON or OFF are printed onto the termination
switch. Only the specified switch positions are permitted.
Switch on the transmitter termination (S1 + S2) and switch off the recei-
ver termination (S3 + S4) if you terminate a RS485 interface.