Commissioning
During commissioning, the dV/dt filter must be logged on using STARTER or via the AOP30
operator panel (p0230 = 2).
Note
Reset when establishing the factory setting
Parameter p0230 is reset when the factory setting is established. The parameter has to be
reset when recommissioning.
8.25
L13, main contactor for Line Connection Modules < 800 A
Availability of option
This option is available for the following S120 Cabinet Modules:
● Line Connection Modules
Description
The Line Connection Modules with option L43 (for Basic Line Modules) include a manually-
operated circuit breaker as a standard feature for rated currents up to 800 A. Option L13 is
needed if a switching element is also required for disconnecting the cabinet from the infeed.
In this case, the contactor is activated from the connected Line Module.
● In conjunction with option L42 (for Active Line Module):
– For a rated current < 605 A (380 to 480 V 3 ph. AC) or < 575 A (500 to 690 V 3 ph.
– For a rated current of 605 A (380 to 480 V 3 ph. AC) or 575 A and 730 A (500 to 690 V
– For a rated current > 605 A (380 to 480 V 3 ph. AC) or > 730 A (500 to 690 V 3 ph.
● In conjunction with option L43 (for Basic Line Module):
– For a rated current < 800 A, option L13 (main contactor) can be ordered.
– For a rated current > 800 A, a circuit breaker is a standard feature in the Line
● In conjunction with option L44 (for Smart Line Module):
– For a rated current < 800 A, option L13 (main contactor) is a standard feature in the
– For a rated current > 800 A, a circuit breaker is a standard feature in the Line
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
AC), the main contactor is included as a standard feature in the Active Interface
Module of the Active Line Module.
3 ph. AC), option L13 (main contactor) is included as a standard feature in the Line
Connection Module.
AC), a circuit breaker is a standard feature in the Line Connection Module.
Connection Module.
Line Connection Module.
Connection Module.
8.25 L13, main contactor for Line Connection Modules < 800 A