8.20.6

X126 PROFIBUS

Table 8- 23
X126 PROFIBUS interface
Pin
1
2
3
4
5
6
7
8
9
Connector type: 9-pin sub D socket
NOTICE
Damage to the Control Unit or other PROFIBUS nodes due to high leakage currents
If a suitable equipotential bonding conductor is not used, significant leakage currents can
flow along the PROFIBUS cable and destroy the Control Unit or other PROFIBUS nodes.
• An equipotential bonding conductor with a cross-section of at least 25 mm² must be
NOTICE
Damage to the Control Unit or other CAN bus nodes due to the connection of a CAN cable
If a CAN cable is connected to the X126 interface, this can destroy the Control Unit or other
CAN bus nodes.
• Do not connect a CAN cable to the X126 interface.
Note
Remote diagnostics
A teleservice adapter can be connected to the PROFIBUS interface (X126) for remote
diagnostics.
The power supply for the teleservice (terminals 2 and 7) can have a max. load of 150 mA.
410
Signal name
Meaning
-
Not assigned
M24_SERV
Power supply for teleservice, ground
RxD/TxD–P
Receive/send data P (B)
CNTR–P
Control signal
DGND
PROFIBUS data reference potential
VP
Supply voltage plus
P24_SERV
Power supply for teleservice, + (24 V)
RxD/TxD–N
Receive/send data N (A)
-
Not assigned
used between components in a system that are located at a distance from each other.
Range
0 V
RS485
TTL
5 V ± 10 %
24 V (20.4 to 28.8 V)
RS485
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A