The line voltage assignments for making the appropriate setting on the transformer for the
internal power supply are indicated in the following tables.
Table 8- 15
Table 8- 16
NOTICE
Property damage due to voltage set too high
If the terminals are not reconnected to the actual line voltage, this can result in damage to
the device when the voltage is set too high.
• Set the terminals in accordance with the actual line voltage.
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A
8.16 K76, auxiliary voltage generating unit in the Line Connection Module
Line voltage assignment for the internal power supply (380 to 480 V AC, 3 phase)
Line voltage range
342 ... 390 V
391 ... 410 V
411 ... 430 V
431 ... 450 V
451 ... 470 V
471 ... 528 V
Line voltage assignments for the internal power supply
(500 to 690 V 3 ph. AC)
Line voltage range
450 ... 515 V
516 ... 540 V
541 ... 560 V
561 ... 590 V
591 ... 630 V
631 ... 680 V
681 ... 759 V
Tap
Adaptation transformer taps
380 V
400 V
415 V
440 V
460 V
480 V
Tap
Adaptation transformer taps
500 V
525 V
550 V
575 V
600 V
660 V
1 to 14, terminals 12 and 13 are jumpered
690 V
1 to 15, terminals 12 and 13 are jumpered
(-T10) LH1 – LH2
1 – 2
1 – 3
1 – 4
1 – 5
1 – 6
1 – 7
(-T10) LH1 – LH2
1 – 8
1 – 9
1 – 10
1 – 11
1 – 12
Options
391