System overview

2.10 System data

2.10
System data
General technical system data
General data
Line voltages and power ranges
Electrical network configurations
Line frequency
Output frequency
Line power factor fundamental
factor
Efficiency
Control method
Fixed speeds
Skipped speed ranges
Braking operation
Degree of protection
Safety class
Overvoltage category
Degree of pollution
Cooling method
Shock protection
Cabinet system
Paint finish
Output data in the basic version, performance enhancement possible with parallel connection.
1)
Compliance with standards
Standards
CE marking
RFI suppression
UL certificate
(only up to 600 V 3AC)
36
380 to 480 V 3 ph. AC, ±10 % (-15 % < 1 min), 5 ... 1150 HP (4.8 ... 800 kW)
500 to 690 V 3 ph. AC, ±10 % (-15 % < 1 min), 75 to 1250 HP (55 to 1200 kW)
Line supplies grounded at the neutral point (TN/TT systems) or ungrounded line
supplies (IT systems)
47 ... 63 Hz
Vector control: 0 ... 600 Hz
Servo control: 0 ... 650 Hz
V/f control: 0 ... 650 Hz
Basic Line Modules:
> 0,96
> 99,0 %
Servo control, vector control with and without encoder or V/f control
15 fixed speeds plus 1 minimum speed, programmable
4, configurable
With regenerative feedback or by additional braking modules and braking resistors
IP20, IP21, IP23 (NEMA1 filtered), IP43 and IP54 (NEMA12 ventilated)
(with option M26 and M27, side panels on the right or left)
Safety class I according to IEC 61800-5-1
III according to IEC 61800-5-1
II according to IEC 61800-5-1
Forced air cooling AF according to IEC 60146
BGV A 3 according to EN 50274
Rittal TS 8, doors with double-bit key, tripartite base plates for cable inlet
RAL 7035 (indoor requirements)
EN 50274, IEC 60146-1, IEC 60204-1, IEC 60529, IEC 61800-2, IEC 61800-3,
IEC 61800-5-1
- EMC Directive No. 2004/108/EC
- Low Voltage Directive No. 2006/95/EC
- Machinery Directive No. 2006/42/EC for Functional Safety
According to EMC product standard for variable-speed drives IEC 61800-3, 

2nd environment (1st environment on request)
According to UL 508A (Option U90) or cUL 508A (Option U91)
Smart Line Modules:
> 0,96
> 98,5 %
1)
1)
Active Line Modules:
variable (set in factory to cos
φ =1)
> 97,5 %
Cabinet Modules NEMA
Manual, 04/2014, A5E03586450A