5.2.4
Cautions on connecting peripheral equipment by way of expansion board or special
adapter
When connecting peripheral equipment (programming tool or GOT [CPU direct connection]) by way of the
FX
-232-BD, FX
3G
the connection channel is not specified with the status below, communication error may occur in the
connected peripheral equipment.
- Set to "K0" the special data register for communication format setting of the channel connecting the
peripheral equipment (CH1: D8400 or D8120, CH2: D8420).
- Set the communication parameter "PLC system [2]" of the channel connecting the peripheral equipment
to "Not set" (as shown in the window below).
5.2.5

Cautions on write during RUN

In FX
PLCs, write during RUN (program changes in the RUN mode) is enabled using the following
3G
programming tools.
Programming tools supporting write during RUN
• English version
Programming tool
*1
GX Works2
(SW DNC-GXW2-E)
*2
GX Developer
(SW D5C-GPPW-E)
*2
FX-PCS/WIN-E
60
-422-BD or FX
-232ADP(-MB), set the connection channel (CH1 or CH2) as follows. If
3G
3U
→ For the operating procedure of and cautions on write during RUN,
Version
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.08J or later
earlier than Ver. 1.40.
Writing in the instruction and device ranges during RUN is supported in FX3G PLCs
Ver. 1.62Q or later
Ver. 1.40.
Writing in the instruction and device ranges during RUN is supported in FX
Ver. 2.00A or later
Ver. 1.00.
Writing in the instruction and device ranges during RUN is supported in FX
Ver. 5.00A or later
Ver. 1.00.
Writing in the instruction and device ranges during RUN is supported in FX
Ver. 8.72A or later
earlier than Ver. 1.10.
Writing in the instruction and device ranges during RUN is supported in FX
Ver. 8.78G or later
Ver. 1.10.
Writing in the instruction and device ranges during RUN is supported in FX
Ver. 3.00 or later
Ver. 1.00.
5 Version Information and Peripheral Equipment Connectability
→ For details, refer to the Data Communication Edition.
Leave this unchecked.
refer to the manual of the used programming tool.
Remarks
5.2 Programming Tool Applicability
2N
1N
3G
3G
1N
PLCs
PLCs
PLCs
PLCs
PLCs