Mitsubishi Electric MELSEC-F FX3G Series User Manual page 5

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

Do not supply power to the [24+] and [24V] terminals (24V DC service power supply) on the main unit or extension
units.
Doing so may cause damage to the product.
Perform class D grounding (grounding resistance: 100
extension units with a wire 2 mm
Do not use common grounding with heavy electrical systems (refer to section 9.3).
Connect the AC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
Connect the DC power supply wiring to the dedicated terminals described in this manual.
If an AC power supply is connected to a DC input/output terminal or DC power supply terminal, the PLC will burn
out.
Do not wire vacant terminals externally.
Doing so may damage the product.
When drilling screw holes or wiring, make sure cutting or wire debris does not enter the ventilation slits.
Failure to do so may cause fire, equipment failures or malfunctions.
Make sure to properly wire the FX
with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
-
The disposal size of the cable end should follow the dimensions described in the manual.
-
Tightening torque should follow the specifications in the manual.
-
Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
Make sure to properly wire to the terminal block (European type) in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
-
The disposal size of the cable end should follow the dimensions described in the manual.
-
Tightening torque should follow the specifications in the manual.
-
Twist the end of strand wire and make sure that there are no loose wires.
-
Do not solder-plate the electric wire ends.
-
Do not connect more than the specified number of wires or electric wires of unspecified size.
-
Affix the electric wires so that neither the terminal block nor the connected parts are directly stressed.
Make sure to properly wire to the FX Series terminal blocks in accordance with the following precautions.
Failure to do so may cause electric shock, equipment failures, a short-circuit, wire breakage, malfunctions, or
damage to the product.
-
The disposal size of the cable end should follow the dimensions described in the manual.
-
Tightening torque should follow the specifications in the manual.
-
Tighten the screws using a Phillips-head screwdriver No.2 (shaft diameter 6mm (0.24") or less). Make sure that
the screwdriver does not touch the partition part of the terminal block.
4. STARTUP AND MAINTENANCE PRECAUTIONS
Do not touch any terminal while the PLC's power is on.
Doing so may cause electric shock or malfunctions.
Before cleaning or retightening terminals, cut off all phases of the power supply externally.
Failure to do so may cause electric shock.
Use the battery for memory backup correctly in conformance to this manual.
-
Use the battery only for the specified purpose.
-
Connect the battery correctly.
-
Do not charge, disassemble, heat, put in fire, short-circuit, connect reversely, weld, swallow or burn the battery,
or apply excessive forces (vibration, impact, drop, etc.) to the battery.
-
Do not store or use the battery at high temperatures or expose to direct sunlight.
-
Do not expose to water, bring near fire or touch liquid leakage or other contents directly.
-
Incorrect handling of the battery may cause heat excessive generation, bursting, ignition, liquid leakage or
deformation, and lead to injury, fire or failures and malfunctions of facilities and other equipment.
-
When replacing the battery, make sure to use our specified product (FX
-
When a battery error occurs ("ALM" LED is lit in red), follow the description in this manual.
Before modifying or disrupting the program in operation or running the PLC, carefully read through this manual and
the associated manuals and ensure the safety of the operation.
An operation error may damage the machinery or cause accidents.
Do not change the program in the PLC from two or more peripheral equipment devices at the same time. (i.e. from
a programming tool and a GOT)
Doing so may cause destruction or malfunction of the PLC program.
Safety Precautions
(Read these precautions before use.)
or less) to the grounding terminal on the main unit and
2
or thicker.
Series main unit and FX
3G
2N
(3)
/FX
Series extension equipment in accordance
3U
-32BL).
3U
Reference
101
123
141
174
177
182
183
186
188
226
248
357
366
Reference
200
311
389