4. Output specifications (Relay output type)
Item
Output Points
Connection type
Output type
External power supply
Output circuit insulation
Indication of output operation
Max. load
Open circuit leakage current
Min. load
Response time
Output circuit configuration

16.2.2 Parts identification and terminal arrangement

Input numbers (X) are assigned to the upper four points, and output numbers (Y) are assigned to the lower
four points.
With cover
252
240V AC or less (250V AC or less when the unit does not comply with CE, UL or cUL standards)
Supplying power to the relay coil will light the LED indicator lamp on panel.
Resistance load
The total resistance load current per common should be as follows:
4 output points/common: 8A or less
Inductive load
OFF ON
ON OFF
Input indicator
lamps (LED lamps)
Output indicator
lamps (LED lamps)
16.2 FX2N-8ER-ES/UL (24V DC Sink/Source Input, Relay Output)
FX
2N
Vertical terminal block (M3 screws)
30V DC or less
Mechanical insulation
→ For cautions on external wiring, refer to Subsection 12.1.3.
5V DC, 2mA (reference values)
Approx. 10ms
Approx. 10ms
Load
DC power
supply unit
Fuse
Without cover
Rear line
extension
connector
16 Input/Output Extension Blocks
-8ER-ES/UL
4 points
Relay
2A/point
80VA
→ For the product life, refer to Subsection 14.4.3.
-
Y