Setting for Battery

The battery is not incorporated in the main unit at shipment from the factory. It is necessary to attach the
optional battery if backup is required.
In addition, the battery mode is set via a parameter.

22.3.1 Attaching the battery

The FX
-40MT/ES is used as the main unit in this example.
3G
1
Turn the power OFF.
2
Remove the top cover (A in the right figure).
When the expansion board, connector conversion adaptor or
memory cassette is attached, remove it.
3
Attach the battery.
Insert the battery connector (B in the right figure) of the battery.
Push the battery into the battery holder (C in the right figure).
Set the battery cable as shown in D in the right figure.
4
Attach the top cover.
When the expansion board, connector conversion adaptor or
memory cassette was removed in the step 2, attach it again.

22.3.2 Setting the battery mode using GX Works2

The following setting using a parameter is required to use the battery.
Note that the battery does not back up the data if the following setting is not provided.
→ For details on GX Developer operating procedure, refer to GX Developer Version 8 Operating Manual.
- On the «PLC system(1)» tab on the "FX parameter" window, check the check box "Use the battery".
(Refer to the window below.)
390
→ For the backup target data, refer to Section 22.1.
Put a check mark to the
check box "Use the battery."