Mitsubishi Electric MELSEC-F FX3G Series User Manual page 132

Hide thumbs Also See for MELSEC-F FX3G Series:
Table of Contents

Advertisement

FX
Series Programmable Controllers
3G
User's Manual - Hardware Edition
3. Wire end treatment
The solderless terminal size depends on the terminal screw size and wiring method.
- Use solderless terminals of the following size.
- Tighten the terminals to a torque of 0.5 to 0.8 N•m.
Do not tighten terminal screws with a torque outside the above-mentioned range. Failure to do so may
cause equipment failures or malfunctions.
In the case of M3 terminal screw
• When one wire is connected to one terminal
6.2mm(0.24")
6.2mm(0.24")
<Reference>
Terminal manufacturer
J.S.T. Mfg. Co., Ltd.
• When two wires are connected to one terminal
6.2mm(0.24")
6.2mm(0.24")
<Reference>
Terminal manufacturer
JJ.S.T. Mfg. Co., Ltd.
*1.
To adapt the LVD directive (EN61010-2-201:2013) of the EC directive, avoid the wiring with two wires
to the built-in terminal, and take an appropriate action such as adding an external terminal.
For the time of compliance with the LVD directive (EN61010-2-201:2013), refer to Requirement for
Compliance with LVD directive.
126
3.2(0.13")
or less
3.2(0.13")
or less
Type No.
FV1.25-B3A
FV 2 -MS3
3.2(0.13")
or less
3.2(0.13")
or less
Type No.
FV1.25-B3A
9 Preparation for Wiring and Power Supply Wiring Procedures
Applicable cable
AWG22 to 16
AWG16 to 14
*1
6.3mm(0.25")
or more
6.3mm(0.25")
or more
Applicable cable
AWG22 to 16
9.2 Cable Connecting Procedures
Terminal
Crimp
screw
terminal
Terminal
Terminal
Certification
Pressure bonding tool
UL Listed
YA-1 (J.S.T. Mfg. Co., Ltd.)
Terminal
Crimp
screw
terminal
Terminal
Certification
Pressure bonding tool
UL Listed
YA-1 (J.S.T. Mfg. Co., Ltd.)