Commissioning
2.16 Temperature sensors for SINAMICS components
Example:
A KTY temperature sensor is connected at the sub D socket X520 on the SMC30 of Encoder
1.
This is parameterized via:
● p0600[0..n] = 1 / p0601[0..n] = 10 / p4601[0..n] = 20
Both temperature channels (X520 and X531) can be used at the same time. In addition to
the above parameterization, the sensor type of the temperature sensor connected at terminal
X531 must be entered in p4600[0..n]. The maximum value is then generated for the motor
temperature and displayed in r0035.
Note
With several encoders, the index [n] of the relevant encoder / encoder data set, via which the
temperature evaluation is performed, must be used.
CU310-2 DP/CU310-2 PN
The Control Unit 310-2 has an integrated SMC30 encoder interface. This encoder interface
is accessed via the 15-pin Sub-D-contact X23 and is evaluated as temperature channel 1.
216
Commissioning Manual, (IH1), 01/2013, 6SL3097-4AF00-0BP3