Relationship Between Alerts, Alert Response Type And Block Error - GE Baker Hughes Masoneilan SVI FF Installation And Operation Manual

Digital positioner
Table of Contents

Advertisement

FF Parameter
FINAL_VALUE_CUTOFF_LO.
ENABLE
FINAL_VALUE_CUTOFF_LO.
CUTOFF_POINT_LO

Relationship Between Alerts, Alert Response Type and Block Error

When an FF block has an error, the system must be configured to report that error. This
configuration task consists of two components:
1. Configuring HI and/or LO Alerts and ensuring they are enabled.
2. Linking each alert to a desired response level. These include:
Device Failure
Maintenance Required
Warning Data
Not Reported
202 |
BHGE
Table 33 Position and Travel Settings (Continued)
SVI FF DTM Field
Cut-Offs Tight Shutoff Enable
checkbox.
Cut-Offs Tight Shutoff Enable
field.
Description
Enables the FINAL_VALUE_CUTOFF_LO.
CUTOFF_POINT_LO field.
If the FINAL_VALUE is more negative than this
value, the valve is forced to its maximum low
value (fully closed).
© 2019 Baker Hughes, a GE company, LLC. All rights reserved.

Advertisement

Table of Contents
loading

Table of Contents