GE DR60 Technical Manual page 97

Table of Contents

Advertisement

4.9.1
Current Analog Inputs
4.9.2
Voltage Analog Inputs
97
Voltage and current analog inputs
Each analog board of the DR60 has 4 current inputs. The inputs types are AC/DC 1A,
AC/DC 5A, AC/DC 1A and 5A (high accuracy for metering) or DC transducer 0-20mA.
Before making the electrical connection, make sure the signal is applied in accordance
with the technical specifications of the equipment.
For information about the analog current inputs specifications, refer to Technical
Specifications Chapter.
Connections shall use screened/shielded cables with insulated flexible wires of at least
2.5 mm² cross section, 8 mm ring terminals, and M3 holes, voltage rating of 300Vrms.
Each analog board of the DR60 has 4 voltage inputs. The inputs types are AC/DC 115V
(for protection), AC/DC 115V (high accuracy for metering) or DC transducer ±10V.
Before making the electrical connection, make sure the signal is applied in accordance
with the technical specifications of the equipment.
DR60
DR60-TM-EN-2A

Hide quick links: