GE DR60 Technical Manual page 27

Table of Contents

Advertisement

DR60
27
LED
Alarm
In Service
Sync
Trigger
The table below shows which events are considered alarms and warnings.
Alarms
Sync NOT OK
Card not detected, invalid
or incompatible
Internal voltage
Internal temperature
No communication
Ethernet interface 1
Color
Indicator
Orange
Warning
Red
Alarm
Green
In Service
Green
Global
Orange
Local
Green
Trigger
Orange
Re-trigger
Data Name
BSE/ALARMSGGIO1.Alm1
BSE/ALARMSGGIO1. Alm2
BSE/ALARMSGGIO1. Alm3
BSE/ALARMSGGIO1. Alm4
BSE/ALARMSGGIO1. Alm5
Meaning
An alarm event that
does not compromise
the DR60 functions was
detected
An alarm event that
compromised DR60
functions was detected
DR60 is working in
perfect conditions
DR60 is synchronized
with the time reference
clock that is
synchronized with
satellite reference
DR60 is synchronized
with the time reference
clock that is not
synchronized with
satellite reference
Any trigger occurred
Any trigger reoccurred
Description
Happens when there are
discrepancies between the
installed boards and the
device CORTEC
Internal voltage
automonitoring alarm
Internal temperature is
abnormal (Out of -10°C to
60ºC)
Loss of communication
with ethernet interface 1
DR60-TM-EN-2A