Bosch PSI 6XXX.350 L1 Series Technical Information page 69

Timer and i/o level
Table of Contents

Advertisement

Electrical connection
7-28
Sequence:
-
A spot must be selected in the I/O field.
-
The gun assigned to the selected spot must be closed.
-
The <Current Check> input signal must be set.
Now, the timer is in <Current Check> mode. No starts or program selections entered in
the I/O field will be accepted.
The program assigned to the selected spot number is started. Primary and secondary
currents are measured. Subsequently, the primary current is checked for any deviation
beyond a specified limit (stated in %) from the secondary current (which is the reference
current in this case). If the primary current exceeds the tolerance limit, an error message
is transmitted.
-
Upon correct completion of the <Current Check>, the <Current scaling/
check finished> signal becomes high and is held until the <Current
Check> input signal is reset.
No WC signal is output during a current check.
If an error occurs:
The notes under "Current Scaling" apply correspondingly.
PSI 6XXX.350 L1
1070 080 067-101 (2001.03) GB