Bosch PSI 6XXX.350 L1 Series Technical Information page 58

Timer and i/o level
Table of Contents

Advertisement

<Weld/No weld external>
1070 080 067-101 (2001.03) GB
PSI 6XXX.350 L1
This signal allows to disable the firing of the weld timer, which may be required for set-up
operations, e.g. ([Sequence] without current).
Apart from the <Weld/No weld external> signal, firing may be controlled by the setting of
Weld/No weld internal relating to all programs and a Weld/No weld setting relating to a
specific program.
These three firing settings are linked by "AND".
With firing deactivated, the [Sequence] of the started program in terms of its timing is the
same as with firing activated. However, no welding operation is performed because there
is no weld current.
-
<Weld/No weld external> :
0 signal ⇒ external firing switched ON via I/O interface.
-
<Weld/No weld external> :
1 signal ⇒ external firing switched OFF via I/O interface.
For all timers
<Weld/No weld
external>
off
off
off
off
on
on
on
on
[1] Caution: Program-specific firing may be active for other programs
Figure 13: Firing settings
Program-specific
Weld
firing
internal
off
off
on
on
off
off
on
on
Electrical connection
Program-specific
Sequence without
off
welding current
Sequence without
on
welding current
Sequence without
off
welding current
Sequence without
on
welding current
Sequence without
off
welding current
Sequence without
on
welding current
Sequence without
off
[1] welding current
Sequence w i t h
on
welding current
sequence
7-17