Commissioning
!
9-6
PSI 6XXX.350 L1
NOTE
If you have access to weld timers which already contain the stepper curves you want to
use, you may load them to the programming terminal and then to your weld timer.
-
Electrode Setup
Check the Electrode Setup or adjust it to the hardware components of your
D
welding equipment.
The input concerning the toroid sensitivity and the [Pressure] should be ad-
justed to the real conditions later on by performing the Scaling procedure.
-
Sequence Setup
Suggestion concerning the settings for all programs:
Deactivate Start Inhibit.
D
Firing setting depending on the requirements of the commissioning work
(with/without welding current).
CAUTION!
When Weld/No weld external has been activated and Weld internal has been switched
on, [Sequences] can be performed with welding current.
Check and/or adjust maximum Weld Time for [1st Weld Time], [2nd Weld
D
Time] and [3rd Weld Time].
Deactivate Control Stopped for KSR mode.
D
Set maximum number of repeats. This number will only be active in those
D
programs in which spot repetition (reweld) has been activated.
Suggestion concerning the settings for the selected program:
Deactivate Start Inhibit.
D
Check the assignment of the electrode to the program.
D
Set the Regulation Mode and the Standard monitoring mode.
D
When commissioning has been completed, these values can be adjusted to
higher requirements of the production process (Mixed mode).
Deactivate spot repetition (reweld).
D
Select single spot mode for the sequence.
D
NOTE
When working with several comparable weld timers, you should perform an Upload
(Backup) for the Basic-Setup and transfer this data later on to the other weld timers using
the Download (Restore) function.