X2 Fire Department Operating Panel / X3 Fire Department Operating Panel - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

43.3.4
Building Technologies
Fire Safety
X4
+
UE Alarm +
+
-
UE Alarm -
UE Rueckm
+
-
FSE -
ST
Fault contact of the transmission device
X2 fire department operating panel / X3 fire department
operating panel
X2 fire department operating panel
Pin
Designation
8
+24V
7
0 V
6
UE ausgel
5
LA ausgel
4
Bf St ab
3
Ak Sign ab
2
BMZ rueckst
1
UE ab
Admissible cable cross-section: 0.2...1.5 mm²
X3 fire department operating panel
PIN
Designation
8
Bf St ab
7
Ak Sign ab
6
BMZ rueckst
5
UE ab
4
UE pruefen
3
Reserve
2
Reserve
1
Admissible cable cross-section: 0.2...1.5 mm²
Fire brigade periphery module FCI2001-D1 [DE]
6
5
200 ... 2k
4
3
2
680
1
Description
Operating voltage (+24 V)
Operating voltage (-)
Transmission transmission triggered
Extinguishing system triggered
Fire controls off
Acoustic signals off
Reset fire control panel
Remote transmission off
Description
Fire controls off
Acoustic signals off
Reset fire control panel
Remote transmission off
Check remote transmission
Reserve output
Reserve input
Not used
43
Pin assignments
ST
3.3k
245
008837_q_en_--
14.05.2012

Advertisement

Table of Contents
loading

Table of Contents