X1 supply

The optional power supply or the external 24 V supply is connected to supply input
X1.
FT2040
U
Sys
FTI2001-A1, supply input for external supply or fitted power supply (optional)
Pin
Designation
10
VSYS–
9
VSYS–
8
VSYS+
7
VSYS+
6
3SRC–
5
3SRC+
4
COMMON
3
#MAINS
2
#CONV
1
#BATT
Admissible cable cross-section: 0.2...2.5 mm²
Fire terminal board
X1
Description
Supply input from the power supply (–)
Supply input from the power supply (–)
Supply input from the power supply (+)
Supply input from the power supply (+)
Input for third supply source (–) [FR]
Input for third supply source (+) [FR]
Ground
Message input from the power supply: Mains failure
Message input from the power supply: Converter fault
Message input from the power supply: Battery fault