Table of contents About this document ................9 Applicable documents ................11 Download center ..................11 Technical terms and abbreviations .............11 Revision history ..................12 Safety ....................15 Safety instructions ..................15 Safety regulations for the method of operation ...........17 Standards and directives complied with............19 2.3.1 CPR conformity and firmware version .........19 Release Notes ...................20...
Page 4
Mounting and installation of the compact control panels ......59 Mounting procedure ................... 59 Mounting and assembling a station ............61 5.2.1 Install rear panel ................. 61 5.2.2 Installing an additional housing ........... 62 5.2.3 Connect the mains cable ............. 64 5.2.4 Installing the operating unit and the operating add-on ....
Page 7
6.11 Installing the CPU card and communication card ........304 6.11.1 Installation in card cage ............304 6.11.2 Switching the network module with dual CPU operation ....306 6.11.3 Ethernet connection ..............307 6.12 Insert license key ..................308 6.13 Installing the operating unit and operating add-on ........309 6.13.1 Installation ................309 6.13.2...
Page 8
8 | 354 Building Technologies 008851_s_en_-- Fire Safety 2016-01-27...
Document 008837 Product data contains the detailed technical description for the components of the FS20 fire detection system. You will find information about assembling and installing the gateway (SIGMANET) and the associated components in the Gateway (SIGMANET) Technical Manual A6V10281424.
Page 10
About this document Applicable documents Source language and reference document ● The source/original language of this document is German (de). ● The reference version of this document is the international version in English. The international version is not localized. Document identification The document ID is structured as follows: ID code Examples...
About this document Applicable documents 1.1 Applicable documents Document ID Title 008836 FS20 Fire Detection System System Description 008837 FS20 Fire Detection System Product Data 009052 FS20 Fire Detection System, Commissioning, Maintenance, Troubleshooting A6V10281424 Technical manual FG2020 1.2 Download center...
About this document Revision history 1.4 Revision history The reference document's version applies to all languages into which the reference document is translated. The first edition of a language version or a country variant may, for example, be version 'd' instead of 'a' if the reference document is already this version. The table below shows this document's revision history: Version Edition date...
Page 13
About this document Revision history Version Edition date Brief description 2013-11-14 Edition for MP5 Change to date format according to ISO 8601 New: Mounting and installation of fire terminal (Touch) FT2080-A1 Installation of module bus cards for AlgoRex migration: ● Line card (AnalogPLUS) FCL2005-A1 ●...
Page 14
About this document Revision history Version Edition date Brief description 03.2010 Second edition MP3.0 for VdS: ● Assignment of manufacturer designation "Scalance" to BT designation 10.2009 First edition MP3.0 for VdS Integration of Scalance module for extended networking: ● Installation arrangement ●...
Safety Safety instructions 2 Safety 2.1 Safety instructions The safety notices must be observed in order to protect people and property. The safety notices in this document contain the following elements: ● Symbol for danger ● Signal word ● Nature and origin of the danger ●...
Page 16
Safety Safety instructions How risk of injury is presented Information about the risk of injury is shown as follows: WARNING Nature and origin of the danger Consequences if the danger occurs ● Measures / prohibitions for danger avoidance How possible damage to property is presented Information about possible damage to property is shown as follows: NOTICE Nature and origin of the danger...
2.2 Safety regulations for the method of operation National standards, regulations and legislation Siemens products are developed and produced in compliance with the relevant European and international safety standards. Should additional national or local safety standards or legislation concerning the planning, mounting, installation,...
Page 18
Modifications to the system design and the products Modifications to the system and to individual products may lead to faults, malfunctioning and safety risks. Written confirmation must be obtained from Siemens and the corresponding safety bodies for modifications or additions. 18 | 354 Building Technologies...
Personal injury or damage to property caused by poor maintenance or lack of maintenance 2.3 Standards and directives complied with A list of the standards and directives complied with is available from your Siemens contact. 2.3.1 CPR conformity and firmware version In order to satisfy Ordinance No.
Safety Release Notes 2.4 Release Notes Limitations to the configuration or use of devices in a fire detection installation with a particular firmware version are possible. WARNING Limited or non-existent fire detection Personal injury and damage to property in the event of a fire. ●...
Setup of the compact control panels Packaging units 3 Setup of the compact control panels 3.1 Packaging units The stations can be delivered in several packaging units. Mounting and assembly are carried out on-site. The delivery consists of the following packaging units: ●...
Setup of the compact control panels Station rear panels (packaging unit) 3.2.1 Rear panel in Eco housing The fire terminal is available in the Eco housing. Figure 1: Fire terminal in Eco rear panel Eco rear panel Opening for cable feed from rear side DIN rail for disconnect terminal blocks Fastening tabs for the cover cap Hole for wall mounting (top)
Setup of the compact control panels Station rear panels (packaging unit) 3.2.2 Rear panel in Standard housing The setup of the different fire control panels in the Standard housing is always identical. Figure 2: Fire control panel in Standard rear panel Standard rear panel Hole for wall mounting (top) Fastening tabs for the cover cap...
Setup of the compact control panels Station rear panels (packaging unit) 3.2.3 Rear panel in Comfort housing With the exception of the periphery board type, the setup of fire control panels FC2020 and FC2040 in the Comfort housing is identical. One exception is the fire control panel FC2040-BB [SE], [FI], which is supplied in the Large housing.
Page 25
Setup of the compact control panels Station rear panels (packaging unit) Recesses for the hinges of the operating unit Mounting holes for operating unit Periphery board Secondary-side cabling of the power supply 10 Recesses for the hinges of the operating add-on 11 Mounting holes for the operating add-on 12 Power supply (150 W) 13 Holes for wall mounting (bottom)
Setup of the compact control panels Station rear panels (packaging unit) 3.2.4 Rear panel in Comfort housing FC2030 Figure 3: Fire control panel FC2030 in Comfort rear panel Comfort rear panel DIN rail for additional components Fastening tabs for the cover cap Openings for cable feed from rear side Holes for wall mounting (top) Recesses for the hinges of the operating unit...
Page 27
Setup of the compact control panels Station rear panels (packaging unit) Secondary-side cabling of the power supply 10 Recesses for the hinges of the operating add-on 11 Mounting holes for the operating add-on 12 Power supply (150 W) 13 Holes for wall mounting (bottom) 14 Strain relief for mains supply cable 15 DIN rail with network separation terminals and for additional components 16 Primary-side cabling of the power supply unit...
Setup of the compact control panels Station rear panels (packaging unit) 3.2.5 Rear panel in Large housing FC2060 as an example of the fire control panel setup in the Large housing: Figure 4: Fire control panel in Large rear panel Large rear panel Holes for wall mounting (top) Fastening tabs for the cover cap...
Page 29
Setup of the compact control panels Station rear panels (packaging unit) Recesses for the hinges of the operating add-on 10 Mounting holes for the operating add-on 11 Power supply (150 W) 12 DIN rail for additional components 13 Holes for wall mounting (bottom) 14 Primary-side cabling of the power supply 15 DIN rail with network separation terminals and for additional components 16 Strain relief for mains supply cable...
Setup of the compact control panels Station rear panels (packaging unit) 3.2.6 Mounting material The following mounting material is supplied with all stations: Rear panel screws Ø 6/40 mm Nylon wall plugs Ø 4.5-6 mm Cable ties 2.4 x 137 mm Philips screws M 3/6 Philips screws M 3/12 ( Edge protection strip 40 x 100 x 1.5 mm...
Setup of the compact control panels Rear panels version [CH] 3.3 Rear panels version [CH] This chapter provides an overview of all components built in the stations of the country variants for Switzerland [CH]. 3.3.1 Eco rear panel of the FT2040-CZ Figure 5: Fire terminal FT2040-CZ in Eco housing Eco rear panel DIN rail (L = 70 mm)
Setup of the compact control panels Rear panels version [CH] 3.3.2 Standard rear panel for FC2020-CZ Figure 6: Fire control panel FC2020-CZ in Standard rear panel Standard rear panel Hole for wall mounting (top) Fastening tabs for the cover cap Openings for cable feed from rear side Recesses for the hinges of the operating unit Mounting holes for operating unit...
Setup of the compact control panels Rear panels version [CH] 3.3.3 Comfort rear panel of the FC2020-CC Figure 7: Fire control panel FC2020-CC in Comfort rear panel Comfort rear panel Holes for wall mounting (top) DIN rail for additional components Fastening tabs for the cover cap Openings for cable feed from rear side Recesses for the hinges of the operating unit...
Page 34
Setup of the compact control panels Rear panels version [CH] Periphery board (2-loop) 10 Cable duct L = 410 mm 11 Recesses for the hinges of the operating add-on 12 Mounting holes for the operating add-on 13 Power supply (70 W) 14 Holes for wall mounting (bottom) 15 Strain relief for mains supply cable 16 DIN rail L = 175 mm with mains separation terminal and socket type 13...
Setup of the compact control panels Rear panels version [CH] 3.3.4 Comfort rear panel of the FC2030-CC Figure 8: Fire control panel FC2030-CC in Comfort rear panel Comfort rear panel FHA2003-A1 Holes for wall mounting (top) DIN rail L = 420 mm with terminal blocks and fuses DIN rail L = 175 mm with 3 mains input terminals Fastening tabs for the cover cap Terminal block, switch module, and 2 fuses for secondary supply...
Page 36
Setup of the compact control panels Rear panels version [CH] Mounting holes for operating unit Terminal block for control pipes Periphery board (2 loops) FCI2002-A1 Recesses for the hinges of the operating add-on Mounting holes for the operating add-on Power supply (150 W) mounted on DIN rail L = 175 mm Holes for wall mounting (bottom) Strain relief for mains supply cable DIN rail L = 175 mm with 7 mains separator terminals and socket type 13...
Setup of the compact control panels Rear panels version [CH] 3.3.5 Comfort rear panel of the FC2040-CC Figure 9: Fire control panel FC2040-CC in Comfort rear panel Comfort rear panel Holes for wall mounting (top) DIN rail for additional components Fastening tabs for the cover cap Openings for cable feed from rear side Recesses for the hinges of the operating unit...
Page 38
Setup of the compact control panels Rear panels version [CH] Periphery board (4 loops) Recesses for the hinges of the operating add-on Mounting holes for the operating add-on Power supply (150 W) mounted on DIN rail Holes for wall mounting (bottom) Strain relief for mains supply cable DIN rail L = 175 mm with mains separation terminal and socket type 13 Cable duct L = 300 mm...
Setup of the compact control panels Operating unit, operating add-on and cover cap (packaging unit) 3.4 Operating unit, operating add-on and cover cap (packaging unit) The operating unit and the optional operating add-on are supplied together with the cover cap as a separate packaging unit. 3.4.1 Operating units and operating add-on The operating unit is part of every station.
Setup of the compact control panels Operating unit, operating add-on and cover cap (packaging unit) Supplied mounting material 4x M5 screws for securing the operating unit 2x M2.5 screws for securing the hinge of the operating unit 1x ribbon cable for the connection from the PMI & mainboard to the periphery board Inscription set or inscription sheet (only for operating unit) You will find additional inscription strips, e.g.
Setup of the compact control panels Location of components 3.5 Location of components This chapter outlines the following components that can be installed in the station: ● Components installed as standard ● Optional components Optional components are supplied in separate packaging units. The figures show the maximum possible scope of equipment.
Setup of the compact control panels Location of components 3.5.2 Standard housing (fire control panels) The fire control panel FC2020 (2-loop) is available in the Standard housing. Figure 14: Components in the Standard housing (fire control panel) Battery kit 9 V [FR] (option) Power supply (70 W) Relay (option) on DIN rail Shield connection terminal blocks [DE] or cable kit (communication),...
Setup of the compact control panels Location of components 3.5.3 Comfort housing (fire control panels) Fire control panels FC2020, FC2030 and FC2040 are available in the Comfort housing. With the exception of the card cage and periphery board type, the setup is identical.
Page 44
Setup of the compact control panels Location of components Loop extensions (FDnet) (option) Periphery board (4-loop) with FC2040 and/or periphery board (2-loop) with FC2020 and FC2030 Power supply (150 W) (fitted horizontally as standard) 10 Additional power supply (150 W) (option) 44 | 354 Building Technologies 008851_s_en_--...
Setup of the compact control panels Location of components 3.5.4 Large housing (fire control panels) The fire control panel FC2060 is available in the Large housing as standard. Fire control panel FC2040-BB [FI], [SE] is also supplied in the Large housing. Figure 16: Example: Components in the Large housing of the fire control panel FC2060 with power supply switched in parallel Relay module (option) on DIN rail...
Setup of the compact control panels Location of components 3.5.5 Operating unit In the operating units, MP3.0 uses the PMI & mainboard FCM2004 and also the PMI & mainboard FCM2027. You will find detailed information about this in document 008837. Figure 17: Components on the operating unit with PMI &...
Setup of the compact control panels Location of components 3.5.6 Position of modules for extended networking 3.5.6.1 Modules in station with Comfort housing Installation arrangement of an Ethernet switch (MM) FN2008-A1 or Security module (firewall) FN2009-A1 taking the example of the FC2040-AA with fire brigade periphery module FCI2001-D1.
Page 48
Setup of the compact control panels Location of components 3.5.6.2 Modules in station with Standard housing Due to space constraints, no Ethernet switch (MM) FN2008-A1 or Security module (firewall) FN2009-A1 can be installed in a fire control panel FC2020. An additional empty housing (Eco or Standard) is needed for this application and is fitted under the fire terminal.
Page 49
Setup of the compact control panels Location of components Housing (Eco) FH2001-A1, empty Mounting kit (switch, Comf.), mounting bracket with two DIN rails FN2008-A1 or FN2009-A1 Fire control panel FC2020 in the housing (Standard) 49 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
Page 50
Setup of the compact control panels Location of components 3.5.6.3 Modules in the fire terminal Due to space constraints, no Ethernet switch (MM) FN2008-A1 or Security module (firewall) FN2009-A1 can be installed in the fire terminal FT2040. An additional empty housing (Eco) is needed for this application and is fitted under the fire terminal.
Page 51
Setup of the compact control panels Location of components Housing (Eco) FH2001-A1, empty Installation kit (switch, comf.) I/O module for alarming the detector contact FN2008-A1 or FN2009-A1 FT2040 fire terminal with optional power supply and batteries 51 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
1 switch ● 1 power socket (Euro) ● 4 expansion bolts with screws for wall mounting ● 1 Siemens/Sinteso sticker each ● 4 screws to fix the cabinet on the base Components Each component is a packaging unit. ● Battery tray (FC2080) ●...
Setup of FC2080 Location of components 4.2 Location of components Figure 21: FC2080, location of components Housing (19'', free-standing cabinet) with base Carrier (19", power supply) with two power supplies (150 W) Power supply kit (150 W, A) Battery tray (19") with batteries Processor unit (19", FC2080) 53 | 354 008851_s_en_--...
Page 54
Setup of FC2080 Location of components Carrier (19", card cage) with two installed card cages (5 slots) Carrier (19", card cage) with one installed card cage (5 slots) and DIN rails Carrier (19", card cage) Carrier (19", option) First power supply group with carrier (19", power supply) and battery tray (19") with batteries. ●...
Setup of FC2080 Setup with one power supply group (sample) 4.3 Setup with one power supply group (sample) FC2080 with one carrier (19", power supply) and the maximum number of card cages. Figure 22: FC2080 with one battery kit and the maximum number of card cages (view of the left-hand side wall and view from the front) FC2080 view of rear panel Processor unit (19", FC2080)
Setup of FC2080 Setup with two power supply groups (sample) 10 Carrier on side wall 11 Carrier (19", power supply) 12 Top grounding terminal 13 FC2080 view of the right-hand side wall 4.4 Setup with two power supply groups (sample) FC2080 with two carriers (19", power supply) and two battery groups.
Page 57
Setup of FC2080 Setup with two power supply groups (sample) Carrier (19", optional) with installed fiber optic cable network module Top battery tray (19") with batteries Bottom battery tray (19") with batteries Base Grounding terminal 10 Carrier 11 Bottom carrier (19", power supply) 12 Top carrier (19", power supply) 13 FC2080 view of the left-hand side wall 57 | 354...
Setup of FC2080 Optional operating units and operating add-ons 4.5 Optional operating units and operating add-ons Operating units and their operating add-ons are separate stations if observed functionally and can be installed in the door of the FC2080 as an option. Figure 24: FC2080 with optional operating unit, view of the inside of the cabinet door Operating unit (option) Operating add-on (option)
Mounting and installation of the compact control panels Mounting procedure 5 Mounting and installation of the compact control panels 5.1 Mounting procedure Mounting takes the following sequence: ● Mounting of rear panel ● Fitting all components ● Assembly of the stations Prerequisites ●...
Page 60
– Add the site number 'No.:' and the commissioning date 'Date:' during commissioning in accordance with EN 54-2. a The station is then ready for commissioning. Siemens Switzerland Ltd Fire Safety & Security Products CH-6301 Zug FC2020 85...265VAC...
Mounting and installation of the compact control panels Mounting and assembling a station 5.2 Mounting and assembling a station 5.2.1 Install rear panel 5.2.1.1 Surface mounting Mounting instructions Any surface irregularities can be compensated with washers or wooden wedges. ● The rear panel is attached to the wall using screws with a diameter of 6 mm.
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.2 Installing an additional housing Separate housings can be mounted for components which do not have any space in the housing or for decentralized supply units. The additional housings are generally mounted right below the stations and attached to them with screws.
Page 63
Mounting and installation of the compact control panels Mounting and assembling a station Mounting steps WARNING Heat bridge between the station and mounting surface caused e.g. by overheating of the batteries Danger of fire ● If you mount the station on a flammable wall, all cut-out sections for the mounting holes must be sealed using the supplied aluminium stickers.
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.3 Connect the mains cable 5.2.3.1 Cable routing Guidelines ● The network cables must be inserted from above. ● The mains lead must be placed along the left side of the housing (observe EMC zone boundary).
Page 65
Mounting and installation of the compact control panels Mounting and assembling a station WARNING Electrical voltage Electric shock ● Before connecting the mains cable, make sure that the cable is current-free. ● Ensure that the mains is secured against inadvertently being switched on. Installation 1.
Page 66
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.3.2 Standard connection Figure 28: Mains connection in the Standard housing (left) and the Comfort housing (right) Mains cable (feed from above) Strain relief clamp Ground on the rear panel Disconnect terminal Primary cabling for power supply Ground cable (yellow/green), pre-assembled...
Page 67
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.3.3 Connection version [CH] Figure 29: Swiss version mains connection in the Standard housing (left) and the Comfort housing (right) Mains cable (feed from above) Strain relief clamp Ground cable (yellow/green) pre-assembled Ground on the rear panel Primary cabling for power supply...
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.3.4 Connection with EU socket Figure 30: Mains wiring with EU socket taking example of fire control panel FC2040-BB Mains cable (feed from above) Strain relief clamp Ground on the rear panel Disconnect terminal Primary cabling for power supply...
Page 69
Mounting and assembling a station 5.2.4.1 Mounting and wiring the operating unit The procedure for mounting the operating unit in the Siemens wall housing is the same for all operating units. The wiring differs according to which options are installed. However, the cable routing is the same for all operating units.
Page 70
Mounting and installation of the compact control panels Mounting and assembling a station Hinge of the operating unit Cable routing to the optional components Cable ties for fixing the cables Operating unit Holes for securing the operating unit Connection (X3) for the ribbon cable on the PMI & mainboard Ribbon cable from the PMI &...
Page 71
Mounting and installation of the compact control panels Mounting and assembling a station Figure 34: Inserting the inscription strips into the operating unit Inscription LEDs Inscription standard keys 1 Inscription standard keys 2 Inscription station type 71 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
Page 72
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.4.2 Install operating add-on For stations in a Comfort housing, operating add-ons are installed in the bottom half of the housing. For stations in an Eco or Standard housing, operating add-ons must be installed in a separate housing.
Mounting and installation of the compact control panels Mounting and assembling a station 5.2.5 Mounting the cover cap Prerequisites ● All options have been installed. ● The operating unit and the operating add-on have been mounted and fastened. ● The batteries have been installed. ●...
Mounting and installation of the compact control panels Periphery board (2-loop) 5.3 Periphery board (2-loop) 5.3.1 Installation The periphery board (2-loop) FCI2002-A1 is mounted in the fire control panels in the factory and only has to be replaced in the event of a repair. X6 X12 X11 X400 Figure 36: Mounting of periphery board (2-loop)
Mounting and installation of the compact control panels Periphery board (2-loop) w Components that make access to the periphery board difficult are removed (e.g. mounting plate). w Connections and plug-in contacts are disconnected and the cables are labelled. w The periphery board is removed. 1.
Page 76
Mounting and installation of the compact control panels Periphery board (2-loop) 5.3.2.2 X6 Horn, alarm and fault monitored outputs Designation Description FAU_OUT Output fault VSYS_O Supply output for consumer fault AL_OUT- Alarm output (-) AL_OUT+ Alarm output (+) SOUND1- Horn output (-) SOUND1+ Horn output (+) Admissible cable cross-section: 0.2…1.5 mm²...
Page 77
Mounting and installation of the compact control panels Periphery board (2-loop) 5.3.2.3 X7 RT alarm and RT fault changeover contacts Designation Description FAU_NC ↑ RT fault ↑ normally closed contact FAU_COM RT fault center tap (common) FAU_NO RT fault ↑ normally open contact AL_NC RT alarm break contact (normally closed) AL_COM...
Page 78
Mounting and installation of the compact control panels Periphery board (2-loop) 5.3.2.4 X8 configurable inputs / outputs 1…4 and supply output 1 Designation Description GND_01 Supply output 1 (–) VSYS_01 Supply output 1 (+) I/O4 Configurable input/output 4 I/O3 Configurable input/output 3 I/O2 Configurable input/output 2 I/O1...
Page 79
Mounting and installation of the compact control panels Periphery board (2-loop) 5.3.2.5 X9 configurable inputs/outputs 5…8 and supply output 2 Designation Description GND_02 Supply output 2 (–) VSYS_02 Supply output 2 (+) I/O8 Configurable input/output 8 I/O7 Configurable input/output 7 I/O6 Configurable input/output 6 I/O5...
Mounting and installation of the compact control panels Periphery board (4 loops) 5.4 Periphery board (4 loops) 5.4.1 Installation The periphery board (4-loop) FCI2004-A1 is already mounted in the fire control panels in the factory and only has to be replaced in the event of a repair. X400 X401 Figure 37: Mounting of the periphery board (4 loops)
Mounting and installation of the compact control panels Periphery board (4 loops) w Components that make access to the periphery board difficult are removed (e.g. mounting plate). w Connections and plug-in contacts are disconnected and the cables are labelled. w The periphery board is removed. 1.
Page 83
Mounting and installation of the compact control panels Periphery board (4 loops) 5.4.2.2 X5 monitored horn outputs 1 and 2 Designation Description SOUND2- Horn output 2 (-) SOUND2+ Horn output 2 (+) SOUND1- Horn output 1 (-) SOUND1+ Horn output 1 (+) Admissible cable cross-section: 0.2…1.5 mm²...
Page 84
Mounting and installation of the compact control panels Periphery board (4 loops) 5.4.2.4 X7 RT alarm and RT fault changeover contacts Designation Description FAU_NC ↑ RT fault ↑ normally closed contact FAU_COM RT fault center tap (common) FAU_NO RT fault ↑ normally open contact AL_NC RT alarm break contact (normally closed) AL_COM...
Page 85
Mounting and installation of the compact control panels Periphery board (4 loops) 5.4.2.5 X8 configurable inputs/outputs 1…12 and supply outputs 1…2 Designation Description GND_01 Supply output 1 (-) VSYS_01 Supply output 1 (+) I/O6 Configurable input/output 6 I/O5 Configurable input/output 5 I/O4 Configurable input/output 4 I/O3...
Page 86
Mounting and installation of the compact control panels Periphery board (4 loops) All inputs/outputs can be connected as follows: Configured as output Configured as input 5.4.2.6 X11 / X21 detector line loop 1 (module 2/3) Designation Description LOOP1_2– ↑ Loop 1 / ↑ stub 2 (–) Connection –...
Mounting and installation of the compact control panels Fire terminal board 5.5 Fire terminal board 5.5.1 Installation The fire terminal board FTI2002-A1 is already mounted in the fire terminal in the factory and only has to be replaced in the event of a repair. Prerequisites ●...
Page 89
Mounting and installation of the compact control panels Fire terminal board Connector for power supply output Vsys Connector for supply input Vsys 2 Connector for supply input Vsys 1 X400 Connector for periphery bus Mounting steps 1. Mount the fire terminal board (2) with the six fixing screws (1) to the screw bushings (3) that are embedded in the rear panel.
Mounting and installation of the compact control panels Fire terminal board 5.5.2 Pin assignments 5.5.2.1 X1 supply The optional power supply or the external 24 V supply is connected to supply input FT2040 Fire terminal board Figure 39: FTI2001-A1, supply input for external supply or fitted power supply (optional) Designation Description VSYS–...
Page 91
Mounting and installation of the compact control panels Fire terminal board 5.5.2.2 X5 supply output Designation Description GND 2 Ground VSYS 2 System supply (+) (1 A/T) GND 1 Ground VSYS 1 System supply (+) (1 A/T) Admissible cable cross-section: 0.2…2.5 mm² GND 2 VSYS 2 GND 1...
Page 92
Mounting and installation of the compact control panels Fire terminal board 5.5.2.3 X6/X7 supply input 2/1 If the fire terminal is supplied by a fire control panel, a redundant supply is needed according to EN 54. For reasons of reliability, the two supply lines must be routed separately.
Page 93
Mounting and installation of the compact control panels Fire terminal board X7, supply input 1 Designation Description VSYS - 1 Ground VSYS - 1 Ground VSYS + 1 System supply (+) VSYS + 1 System supply (+) Admissible cable cross-section: 0.2…2.5 mm² VSYS -1 VSYS -1 VSYS +1...
Mounting and installation of the compact control panels Power supply (70 W) 5.6 Power supply (70 W) In fire control panels, the power supply (70 W) FP2001-A1 or FP2015-A1 is always built-in. In fire terminals and additional housings, the power supply (70 W) is an option.
Mounting and installation of the compact control panels Power supply (70 W) 5.6.1 Installation The 70 W power supply FP2001-A1 or the FP2015-A1, which is identical in construction, is only installed in Standard and Eco housings. Figure 41: Example: Installation of the power supply (70 W) in the Standard housing Fixing screw (under mains connection terminal X1) Power supply (70 W) FP2015 Guides for the distance pins of the power supply unit...
Mounting and installation of the compact control panels Power supply (70 W) 5.6.2 Pin assignments 5.6.2.1 X1 mains connection Designation Description Ground (protective conductor PE) Neutral conductor External conductor (L1) Admissible cable cross-section: 0.2…2.5 mm² 5.6.2.2 X2 Power supply and signal lines FP2001 Designation Description Battery...
Page 97
Mounting and installation of the compact control panels Power supply (70 W) 5.6.2.3 X2 battery supply and signal lines Designation Description Battery Detection line (#BATT): Battery fault Not used Mains Detection line (#MAINS): Mains fault Not used Usys + System supply (VSYS+) Usys –...
Mounting and installation of the compact control panels Power supply (150 W) 5.7 Power supply (150 W) The description for installing the power supply (150 W) applies to both versions of the power supply, for the type A4 and for the type A5. Only the wiring of the network connection and when switching in parallel are different.
Page 99
Mounting and installation of the compact control panels Power supply (150 W) Mounting in the power supply Figure 42: Installation of the 150 W power supply in the Comfort housing DIN rail for power supply Fixing screws for DIN rail Power supply (150 W) FP2004-A1 Bottom fixing screw Retaining bracket...
Page 100
Mounting and installation of the compact control panels Power supply (150 W) Installing the temperature sensor Figure 43: Position of temperature sensor in housing Batteries Temperature sensor Luster terminal Connection cable to the power supply Connection terminal X11 to the power supply for the temperature sensor Approximate distance to the lower edge of the power supply: 20 mm Approximate distance to the side wall of the power supply: 5 mm 1.
Mounting and installation of the compact control panels Power supply (150 W) 5.7.2 Fitting an additional power supply (150 W) The additional power supply (150 W) FP2005-A1 in the Comfort housing is installed vertically along with the existing power supply to save space. Preparatory work Before the additional power supply FP2005-A1 can be installed, the existing power supply and the DIN rail must be removed as described in the previous chapter.
Page 102
Mounting and installation of the compact control panels Power supply (150 W) Mounting steps 1. At the bottom of the power supply (4), insert the distance pins into the guide on the rear panel as shown. 2. Fasten the power supply (2 and 3) to the lug at the top (1) using the Phillips screw.
Mounting and installation of the compact control panels Power supply (150 W) Mounting steps 1. Position the luster terminal (3) in accordance with the dimensions (x) and (y) and secure the luster terminal with the supplied adhesive mount. 2. Connect the assembled cable (4) to the luster terminal (3) and to the connection terminal X11 (5) of the power supply according to the pin assignment shown in the next chapter.
Page 104
Mounting and installation of the compact control panels Power supply (150 W) 5.7.3.3 X11 monitoring signals Designation Description Not used Not used Control line for even current distribution (only when switching in parallel) Control line for even current distribution (only when switching in parallel) Connection for temperature sensor (master only) Connection for temperature sensor (master only) Signaling: Battery fault (↑...
Page 105
Mounting and installation of the compact control panels Power supply (150 W) 5.7.3.4 Parallel switching of two supply units NOTICE Damage to the power supply Different versions (A4/A5) of the power supply (150 W) may not be switched in parallel. SV 24V-150W-A4 MASTER NTC 4.7 kΩ...
Mounting and installation of the compact control panels Power supply (150 W) Cable tree to periphery board or fire terminal board Existing cable tree (connection for master power supply) Additional cable tree for the second power supply (slave) Additional fused terminal (F2) on the DIN rail ●...
Page 107
Mounting and installation of the compact control panels Power supply (150 W) 5.7.4.2 X8 output voltage Designation Description Connection for battery, current limited via internal battery fuse F2 (without parallel I-begr. switching) Connection for battery, not current limited (when switching in parallel: Fuse in the I-unbegr.
Page 108
Mounting and installation of the compact control panels Power supply (150 W) 5.7.4.3 X11 monitoring signals Designation Description Control line B for even current distribution (only when switching in parallel) Control line B for even current distribution (only when switching in parallel) Control line A for even current distribution (only when switching in parallel) Control line A for even current distribution (only when switching in parallel) Connection for temperature sensor (master only)
Page 109
Mounting and installation of the compact control panels Power supply (150 W) 5.7.4.4 Parallel switching of two supply units SV 24V-150W-A5 MASTER NTC 4.7 kΩ #BATT #MAINS COMMON VSYS+ VSYS- I-begr. T6.3A 12 A ... 20 A I-unbegr. +24V +24V +24V Battery +24V...
Page 110
Mounting and installation of the compact control panels Power supply (150 W) ● The connection lines marked in bold of the additional cable tree (3) and the existing cable tree (2) must be wired again when installing the second power supply (slave).
Page 111
Mounting and installation of the compact control panels Power supply (150 W) 5.7.4.5 Parallel switching of three supply units SV 24V-150W-A5 MASTER NTC 4.7 kΩ #BATT #MAINS COMMON +VSYS -VSYS I-begr. T6.3A 12 A ... 20 A I-unbegr. +24V +24V +24V Battery +24V...
Page 112
Mounting and installation of the compact control panels Power supply (150 W) ● The connection lines marked in bold of the additional cable tree (3 and 5) and the existing cable tree (2) must be wired again when installing the second power supply (slave).
Mounting and installation of the compact control panels Battery kit (9 V) [FR] 5.8 Battery kit (9 V) [FR] 5.8.1 Installation in the Eco and Standard housings Figure 51: Mounting of battery kit FCA2010-F1 in Eco and Standard housing Power supply (70 W), if installed Battery holder Fixing screws Battery, 9 V block type E...
Mounting and installation of the compact control panels Battery kit (9 V) [FR] 5.8.2 Installation in Comfort housing Figure 52: Mounting of battery kit FCA2010-F1 in Comfort housing Battery, 9 V block type E Fixing screws Battery holder X1 Battery kit connection (9 V) Mounting steps 1.
Mounting and installation of the compact control panels Loop extension 5.10 Loop extension 5.10.1 Installation The loop extensions (FDnet) FCI2003-A1 are mounted onto the periphery board. The slots are located next to the corresponding detector line connections. The installation of the two loop extensions on the periphery board (4-loop) is identical.
Mounting and installation of the compact control panels Relay module 5.11 Relay module Figure 55: Mounting of relay module DIN rail Relays Z3B171 Locking clamp for the relays Fixing screws for the DIN rail 1. Insert the relays (2) on the DIN rail (1) and press them down until they snap into place.
Mounting and installation of the compact control panels Mounting plate 5.12 Mounting plate The mounting plate FHA2007-A1 is used to hold components that have to be installed above the periphery board. It is supplied in a disassembled state and in a separate packaging unit.
Page 121
Mounting and installation of the compact control panels Mounting plate Hinged bracket Fork head (2 pieces) for mounting the hinge bracket Counternut M 5 (2 pieces) Spacer bolts (2 pieces) 10 Threaded holes in rear panel for spacer bolts 11 Fastening clamp, installation position (2 pieces) 12 Spacer bolts, assembled and mounted 13 Fastening clamp (fixed position) 1.
Mounting and installation of the compact control panels Mounting plate 5.12.2 Installation of the mounting plate in the Large housing Figure 57: Installing the mounting plate FHA2007-A1 in the Large housing (FC2060) Periphery board (4 loops) Mounting hole in the rear panel for spacer Spacer Fixing screw for mounting plate Assembled mounting plate...
Page 123
Mounting and installation of the compact control panels Mounting plate Mounting steps 1. Screw the spacer (3) to the rear panel (2) to the right below the periphery board (1). 2. Assemble the mounting plate (5) and install the mounting plate according to the instructions in the previous chapter (Installation for the Standard and Comfort housings).
Mounting and installation of the compact control panels Fire brigade periphery module [DE] 5.13 Fire brigade periphery module [DE] 5.13.1 Installation The fire brigade periphery module FCI2001-D1 can be mounted at different positions depending on the station type and equipment: ●...
Page 125
Mounting and installation of the compact control panels Fire brigade periphery module [DE] X402 X401 Figure 59: Mounting of the fire brigade periphery module Spacer sleeves (5 pieces) (only required for mounting on the mounting plate) 3 fixing screws at top Fire brigade periphery module FCI2001-D1 2 fixing screws at bottom Connection for fire brigade operating panel...
Mounting and installation of the compact control panels Fire brigade periphery module [DE] 5.13.2 Pin assignments Inputs and outputs which are not used do not require termination. 5.13.2.1 X2 fire brigade operating panel / X3 fire brigade operating panel X2 fire brigade operating panel Designation Description +24V...
Page 127
Mounting and installation of the compact control panels Fire brigade periphery module [DE] +24V UE ausgel LA ausgel Bf St ab Ak Sign ab BMZ rueckst UE ab Bf St ab Ak Sign ab BMZ rueckst UE ab UE pruefen Reserve Reserve The connection details correspond to the FBF Type Wiesmeier FBF0770...
Page 128
Mounting and installation of the compact control panels Fire brigade periphery module [DE] 5.13.2.2 X4 remote transmission /release element Designation Description +24V Operating voltage (+24 V) ↑ UE Alarm+ ↑ Remote transmission/device alarm (+) UE Alarm- Remote transmission/device alarm (-) UE Rueckm Remote transmission /device acknowledgement (+) FSE+...
Page 129
Mounting and installation of the compact control panels Fire brigade periphery module [DE] 5.13.2.3 X5 fire brigade key depot Designation Description Sabotage + Tamper monitoring (+) Sabotage - Tamper monitoring (-) Entriegel + Unlocking (+) Entriegel - Unlocking (-) Riegelkont + Latch contact (+) Riegelkont - Latch contact (-)
Page 130
Mounting and installation of the compact control panels Fire brigade periphery module [DE] 5.13.2.4 X6 intrusion detection system / local alarm / identification lamp Designation Description Ke Leuchte + Identification lamp (+) Ke Leuchte - Identification lamp (-) Oertl Alarm + Local alarm (+) Oertl Alarm - Local alarm (-)
Mounting and installation of the compact control panels Network module (SAFEDLINK) 5.14 Network module (SAFEDLINK) 5.14.1 Installation This component is installed in exactly the same way as for the operating units with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027. If you are installing only one network module (SAFEDLINK) FN2001-A1, you must do so in the left-hand slot (X13).
Page 132
Mounting and installation of the compact control panels Network module (SAFEDLINK) Mounting steps 1. When shielded cables are used, mount the two cable glands (5) with the nuts (4) on the flange between the fastening tabs (3). These are needed to secure the shielding.
Mounting and installation of the compact control panels Installing the fiber optic cable network module 5.15 Installing the fiber optic cable network module 5.15.1 Replacing the DIN rail clip The identical fiber optic cable network modules FN2006-A1 and FN2007-A1 can be installed on a DIN rail either horizontally or vertically.
Limitations ● The fiber optic cable network module cannot be mounted on the flanges in all FS20 compact control panels because there is no suitable method of fastening it in the rear panels or on the mounting plate. ● Horizontal installation with a DIN rail on a mounting plate is not possible because there are no installation parts (the DIN rail cannot be ordered with installation material).
Mounting and installation of the compact control panels Installing the fiber optic cable network module 5.15.3 Pin assignments 5.15.3.1 Power A and B sockets, fault contact The 5-pin connector for the power supply is supplied with the fiber optic cable network module.
Page 137
Mounting and installation of the compact control panels Installing the fiber optic cable network module Connector with housing Socket on fiber optic cable network module Connector without housing Cover cap (open) 360° shielding 137 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
Page 138
Mounting and installation of the compact control panels Installing the fiber optic cable network module 5.15.3.2 EF1/EF2 sockets for SAFEDLINK wiring The 3-pin connector for the FCnet/SAFEDLINK connection is supplied with the fiber optic cable network module. EF1 socket, FCnet A1/B1 Designation Description FCnet line 1 (-)
Page 139
Mounting and installation of the compact control panels Installing the fiber optic cable network module The feed line of the electric FCnet can be either shielded or unshielded. If the feed line is shielded, cable glands must be used for the ↑ network module (SAFEDLINK).
Page 140
Mounting and installation of the compact control panels Installing the fiber optic cable network module 5.15.3.3 Fiber optic cable connection ● If the fiber optic cable network module is mounted in the ↑ station, then only one supply must be connected. ●...
Page 141
Mounting and installation of the compact control panels Installing the fiber optic cable network module Fiber optic cable wiring ● The accessible laser radiation is harmless. It corresponds to Laser Class 1 in accordance with IEC 60825/ANSI Z136. ● The fiber optic cable is wired cross-wise: –...
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16 Installing an Ethernet switch (modular) FN2012 Malfunctions during a partial upgrade Ethernet switch (modular) FN2012 is not compatible with Ethernet switch (MM) FN2008 and so may only be used in panels ≥MP6. 5.16.1 Installation of Ethernet modules The Ethernet switch (modular) must be equipped with Ethernet modules.
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.2 DIN rail clip mounting The diagram below shows how to mount the DIN rail clip on the FN2012. 2x countersunk screws DIN rail clip in mounting position 4x spacers with thread for fixing the DIN rail clip Ethernet switch (modular) FN2012 Flange with retaining clamp...
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.3 Installing mounting kit FHA2029 The mounting kit (switch) is required to install Ethernet switch (modular) FN2012. VdS does not allow the Ethernet switch to be installed in any other way. If the stations do not provide enough room to install a mounting bracket, the Ethernet switch must be installed in an empty housing.
Page 145
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 Types of installation ● The small mounting bracket is intended for installation in an empty housing and can be installed on both sides, i.e., in either the left or the right installation position.
Page 146
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.3.1 Installation in empty and Comfort housing The process of installing the small mounting bracket from mounting kit FHA2029 is identical for all empty housings and for stations in Comfort housings. Figure 71: Installing the small mounting bracket in a Comfort housing Figure 72: Small mounting bracket, installed in the Comfort housing 146 | 354...
Page 147
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 Empty Comfort housing Small mounting bracket Lugs for recesses for securing the power supply (70W) DIN rail installed Retaining bracket installed 3x fixing screws for mounting bracket 3x sleeves for fixing to spacer 3x holes in mounting bracket for spacer 3x spacers with thread in rear panel...
Page 148
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.3.2 Installation in a station with a Large housing Figure 73: Screwing the large mounting bracket onto the Large rear panel Figure 74: Large mounting bracket installed without supply 148 | 354 Building Technologies 008851_s_en_--...
Page 149
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 Figure 75: Supply installed on top of large mounting bracket Housing (Large) Large mounting bracket U-rail installed Retaining bracket installed 3x fixing screws for mounting bracket 3x holes for fixing screws 3x threaded holes in rear panel Mounting flange for the power supply (150 W)
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.4 Installing Ethernet switch FN2012 To ensure that installation conforms to VdS requirements, the FN2012 must be mounted vertically on a mounting bracket from mounting kit (switch) FHA2029 . The connections for the fiber-optic cables must be aligned so they point upward.
Page 151
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.4.2 FN2012 in a station with a Comfort housing Figure 77: Small mounting bracket installed in a Comfort housing 151 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
Page 152
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 Figure 78: FN2012 in the Comfort housing Comfort housing Small mounting bracket from mounting kit FHA2029 DIN rail with retaining bracket FN2012 w The DIN rail clip is mounted on the FN2012. 1.
Page 153
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.4.3 FN2012 in a station with a Large housing Figure 79: FN2012 mounted in the Large housing Housing (Large) Large mounting bracket from mounting kit FHA2029 DIN rail with retaining bracket FN2012 Power supply (150 W)
Installing an Ethernet switch (modular) FN2012 5.16.5 Wiring 5.16.5.1 Wiring overview The figure shows typical usage of the Ethernet switch in an FS20 station with all connections and in an optical Ethernet ring. All the connections shown are current- limited and monitored.
Page 155
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.5.2 MoNet bus connection Preparing the FN2012 for the MoNet bus connection Figure 81: Breaking out the MoNet bus cover plate Use a screwdriver to carefully remove the cover plate from the MoNet connector, as shown in the figure.
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.6 Pin assignments 5.16.6.1 'POWER' connector strip The 'POWER' connector is only used if power cannot be supplied via the MoNet bus or PoE. Generally, this is only the case if the Ethernet switch (modular) is installed remotely in another device.
Page 157
Mounting and installation of the compact control panels Installing an Ethernet switch (modular) FN2012 5.16.6.2 'FAULT' connector strip The fault output is a potential-free relay contact which, depending on the configuration, can be used to report fault conditions by interrupting the contact. If the FN2012 is switched off, the relay contact is deactivated (opened).
Mounting and installation of the compact control panels Connection module (card cage) 5.17 Connection module (card cage) 5.17.1 Installation This component is installed in exactly the same way as for the operating units with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027. The connection module (card cage) FCA2006-A1 is always needed in conjunction with the card cage (2 slots) or card cage (5 slots).
Mounting and installation of the compact control panels Card cage 5.18 Card cage 5.18.1 Installation The card cage is used to hold module bus cards and is fitted in fire control panels FC2030 and FC2060 in the factory: ● Card cage (2 slots) FCA2007-A1 in fire control panel FC2030 ●...
Page 160
Mounting and installation of the compact control panels Card cage Installation of card cage (5 slots) FCA2008-A1 in FC2060 Figure 85: Installation of card cage (5 slots) Rear panel (FC2030) or mounting plate (FC2060) Periphery board Card cage housing cover (EMC protection) Card cage Mounting holes for screws (2) in card cage housing Mounting holes for screws (4 pieces) in printed circuit board...
Mounting and installation of the compact control panels Card cage 5.18.2 Pin assignment of the card cage (2 slots) 5.18.2.1 Views of card cage (2 slots) X22 X21 X501 Figure 86: PCB view of card cage (2 slots) FCA2007-A1 Element Des.
Page 162
Mounting and installation of the compact control panels Card cage Element Des. Function Connector Connector for degraded mode indicator [AT] of module bus card 1 Degraded mode Connector for degraded mode indicator [AT] of module bus card 2 Internal bus X501 Connector for module bus input 5.18.2.2 X9 supply...
Mounting and installation of the compact control panels Card cage 5.18.3 Pin assignment of the card cage (5 slots) 5.18.3.1 Views of card cage (5 slots) X51 X42 X41 X32 X31 X22 X21 X501 X500 Figure 87: PCB view of card cage (5 slots) FCA2008-A1 Element Des.
Page 164
Mounting and installation of the compact control panels Card cage Element Des. Function Connection terminals System supply connection Connection terminals for module bus card 1 Connection terminals for module bus card 1 Connection terminals for module bus card 2 Connection terminals for module bus card 2 Connection terminals for module bus card 3 Connection terminals for module bus card 3 Connection terminals for module bus card 4...
Page 165
Mounting and installation of the compact control panels Card cage 5.18.3.3 X11…X52 connection terminals for the module bus card The module bus card determines the PIN assignment of the four connectors. You will find the pin assignments in the description of the corresponding module card. The assignment of the connector is: ●...
Mounting and installation of the compact control panels Module bus cards 5.19 Module bus cards 5.19.1 Installation The module bus cards are installed in the card cages of fire control panels FC2030, FC2060, FC2080 or gateway (SIGMANET) FG2020. The following module bus cards are available: ●...
Mounting and installation of the compact control panels Module bus cards 1. Remove the housing cover of the card cage (2) by loosening the four fixing screws (1). 2. Insert the module bus card required (3) into the slot required as shown in the figure.
Page 168
Mounting and installation of the compact control panels Module bus cards Element Des. Function Slots Connector strip for module bus card 1 Connector strip for module bus card 2 Connection terminals System supply connection Connection terminals for module bus card 1 Connection terminals for module bus card 1 Connection terminals for module bus card 2 Connection terminals for module bus card 2...
Page 169
Mounting and installation of the compact control panels Module bus cards 5.19.2.2 Views of card cage (5 slots) X51 X42 X41 X32 X31 X22 X21 X501 X500 Figure 90: PCB view of card cage (5 slots) FCA2008-A1 Element Des. Function Slots Connector strip for module bus card 1 Connector strip for module bus card 2...
Page 170
Mounting and installation of the compact control panels Module bus cards Element Des. Function Connection terminals System supply connection Connection terminals for module bus card 1 Connection terminals for module bus card 1 Connection terminals for module bus card 2 Connection terminals for module bus card 2 Connection terminals for module bus card 3 Connection terminals for module bus card 3...
Page 171
Mounting and installation of the compact control panels Module bus cards 5.19.2.3 Connection terminals of line card (FDnet/C-NET) in card cage The ↑ line card (FDnet / C-NET) FCL2001-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 172
Mounting and installation of the compact control panels Module bus cards 5.19.2.4 Connection terminals of line card (collective) in card cage The ↑ line card (collective) FCL2002-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 173
Mounting and installation of the compact control panels Module bus cards 5.19.2.5 Connection terminals of line card (MS9i) in card cage The ↑ line card (MS9i) FCL2003-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 174
Mounting and installation of the compact control panels Module bus cards 5.19.2.6 Connection terminals of line card (AnalogPLUS) in card cage The ↑ line card (AnalogPLUS) FCL2005-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 175
Mounting and installation of the compact control panels Module bus cards 5.19.2.7 Connection terminals of line card (interactive) in card cage The ↑ line card (interactive) FCL2006-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 176
Mounting and installation of the compact control panels Module bus cards 5.19.2.8 Connection terminals of line card (interactive, Ex) in card cage The ↑ line card (interactive, Ex) FCL2007-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 177
Mounting and installation of the compact control panels Module bus cards 5.19.2.9 Connection terminals for the I/O card (programmable) in the card cage The I/O card (programmable) FCI2008-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 179
Mounting and installation of the compact control panels Module bus cards Example for pin assignment at slot 1 Connector Designation Description FIRE_OUT_1+ Horn/alarm monitored FIRE_OUT_1- FIRE_OUT_2+ Horn/alarm monitored FIRE_OUT_2- FIRE_OUT_3+ Horn/alarm monitored FIRE_OUT_3- FIRE_OUT_4+ Horn/alarm monitored FIRE_OUT_4- FIRE_OUT_5+ Horn/alarm monitored FIRE_OUT_5- FIRE_OUT_6+ Horn/alarm monitored...
Page 180
Mounting and installation of the compact control panels Module bus cards Switching variants for monitored alarm and horn outputs with decoupled load (EN 54) Example horn output FireOutput2- Rload Reol Rcable FireOutput2+ Example alarm output FireOutput1- Rload Reol Rcable FireOutput1+ Figure 91: Switching examples for monitored alarm and horn outputs with decoupled load (EN 54) Rload Load resistance...
Page 181
Mounting and installation of the compact control panels Module bus cards 5.19.2.11 Connection terminals for the I/O card (RT) in the card cage The I/O card (↑ RT) FCI2007-A1 determines the PIN assignment of the four connection terminals in the card cage. External connections on the card cage using the example of module bus card 1 with the associated connection terminals X11 and X12: ●...
Page 182
Mounting and installation of the compact control panels Module bus cards Switching for RE response in accordance with ↑ VdS 27V2 FireOutput1+ UE _Rückmeldung Figure 93: Switching for RE response in accordance with VdS Fault contact of the transmission device Switching for monitored remote transmission Rcable UE_Fault+...
Page 183
Mounting and installation of the compact control panels Module bus cards Switching variants for monitored alarm and horn outputs with load resistance monitoring (VdS) Example horn output FireOutput2- Rload Rcable FireOutput2+ Example alarm output FireOutput1- Rload Rcable FireOutput1+ Figure 96: Switching examples for monitored alarm and horn outputs with load resistance monitoring (VdS) Rload Load resistance...
Page 184
Mounting and installation of the compact control panels Module bus cards Switching for relays ↑ RT alarm and RT fault FAU_NC FAU_COM FAU_NO AL_NC AL_COM AL_NO Figure 98: Switching for relays RT Alarm and RT Fault Remote transmission FAU_… Configured as RT fault relay output - ↑...
Mounting and installation of the compact control panels RS232 / RS485 module 5.20 RS232 / RS485 module 5.20.1 Installation This component is installed in exactly the same way as for the operating units with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027. The serial modules include: ●...
Page 186
Mounting and installation of the compact control panels RS232 / RS485 module Figure 100: Sample installation of the serial modules RS232 module in slot X14 Fixing screw (2 pieces) Mounting links on support plate RS485 module in slot X19 Slot 1 on the operating unit with RS232 module Slot 2 on the operating unit with RS485 module Connection terminal on RS232 module Connection terminal on RS485 module...
Mounting and installation of the compact control panels RS232 / RS485 module 5.20.2 Pin assignments You will find information on connecting the event printer in the chapter 'Event printer'. 5.20.2.1 X3 DTE HOST on RS282 module Designation Description ← DCD Data Carrier Detected ←...
Page 188
Mounting and installation of the compact control panels RS232 / RS485 module 5.20.2.2 X2 on RS485 module Designation Description RS485_A Line A RS485_B Line B Not connected Not connected Admissible cable cross-section: 0.2…1.5 mm² RS485_A RS485_B T1 First participant Tn Last participant *) Stub lines must not exceed 20 m! ●...
Mounting and installation of the compact control panels Event printer 5.21 Event printer 5.21.1 Installation This component is installed in exactly the same way as for the operating units with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027. The event printer FTO2001-A1 is an option and can be installed either in the operating unit or in the operating add-on, depending on the station design.
Page 190
Mounting and installation of the compact control panels Event printer Mounting steps Check the installation site carefully Depending on the station type it is possible that the depth is insufficient for the event printer. This must be checked especially if operating add-ons are used, as the batteries are installed immediately behind the event printer.
Mounting and installation of the compact control panels Event printer 5.21.2 Pin assignments 5.21.2.1 Connection on printer side Product version (ES) 01 Figure 102: Rear view ES01 Product version (ES) 02 ES02: Serial interface settings + – RS232 RS232 Rear view ES02 View from below Fastening clamps Supply connection...
Page 192
Mounting and installation of the compact control panels Event printer 5.21.2.2 Connection on station side The event printer must be directly connected to the power supply. Connecting the event printer to the power supply (70 W) Connector From printer Power supply terminal X2 Positive supply (red) =>...
Page 193
Mounting and installation of the compact control panels Event printer Connection of event printer to RS232 module Connector From printer Terminal X3 of RS232 module Data (white) => (X3) PIN 6 (CTS) Data (brown) => (X3) PIN 4 (RXD) Data (green) =>...
Mounting and installation of the compact control panels Key switch (Kaba) FTO2005-C1 5.22 Key switch (Kaba) FTO2005-C1 This component is installed in exactly the same way as for the operating units with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027. Figure 103: Installing the guard ring for the key switch on the foil side Foil side of the operating unit Guard ring for the key switch...
5.23 Redux module [DE] 5.23.1 Installation The Redux module RGQ:FAT-Redux-FS20 is an option for redundantly activating the fire brigade indication panel (FAT) [DE]. It is fitted on the DIN rail in the fire control panel.
Mounting and installation of the compact control panels Redux module [DE] 5.23.2 Pin assignments The pin assignment of the Redux module is listed in the manual of the Redux module. During connection please observe the following: ● The data cables of the Redux module are connected to the RS485 interface. ●...
Mounting and installation of the compact control panels Input/output module FDCIO224 [DE] 5.24 Input/output module FDCIO224 [DE] 5.24.1 Installation The input/output module FDCIO224 has four potential-free contact inputs and four control outputs for VdS-compliant connection of the VdS extinguishing interface. For this application it must be installed in the fire control panel.
Mounting and installation of the compact control panels Sounder module 5.25 Sounder module 5.25.1 Installation Sounder module FCI2005-A1 is fitted in the fire control panel. The sounder module can be screwed flat onto the rear panel or mounting plate or engaged on the DIN rail by means of the enclosed mounting feet FDCM291.
Mounting and installation of the compact control panels Sounder module 5.25.2 Pin assignments 5.25.2.1 X1 supply input and sounder input from the periphery board X1 sounder module Periphery board Periphery board 2 loops 4 loops Designation Description Designation Designation +Vsys X8-5 VSYS_01 (+) X8-7...
Page 200
Mounting and installation of the compact control panels Sounder module 5.25.2.3 X3 sounder 3 and 4 outputs Designation Description S4 out+ Sounder output 4 (+) S4 out- Sounder output 4 (-) S3 out+ Sounder output 3 (+) S3 out- Sounder output 3 (-) Admissible cable cross-section: 0.08…1.5 mm²...
Page 201
Mounting and installation of the compact control panels Sounder module 5.25.2.4 Cascading of two sounder modules A maximum of two sounder modules may be cascaded. X6 / X5 Sound In- S2 out+ SOUND1- kΩ Sound In+ SOUND1+ S2 out- Ground S1 out+ kΩ...
Mounting and installation of the compact control panels Modes of mounting for modules 5.26 Modes of mounting for modules Modules like the input/output module (transponder) or the sounder module can be fitted in different ways. The following modes of mounting are possible: ●...
Mounting and installation of the compact control panels Modes of mounting for modules 5.26.1 Mounting on DIN rail or mounting plate NOTICE Short mounting distance Module overheating ● There must be an air gap of at least 1 cm above the cover cap of the module. ●...
Mounting and installation of the compact control panels Modes of mounting for modules 5.26.2 Mounting in housing FDCH221 When installing the module in the housing FDCH221, proceed as follows: 1. Break out the cable entries. 2. Mount the housing on a flat surface. The housing cover is transparent so the LEDs can be seen at all times.
Mounting and installation of the compact control panels RT interface [NL] 5.27 RT interface [NL] 5.27.1 Installation The RT interface FCI2005-A1 can be mounted at different positions depending on the station type and equipment: ● In the Comfort housing to the left of the periphery board, if there is sufficient space ●...
Page 206
Mounting and installation of the compact control panels RT interface [NL] 1. Mount the RT interface (4) to the mounting plate (2) or the rear panel (observe correct installation position) as shown using the five fixing screws (3). The five spacer bolts (1) must be used when installing on the mounting plate.
Mounting and installation of the compact control panels RT interface [NL] 5.27.2 Pin assignments 5.27.2.1 X1 switching contacts relays 1…5 Designation Description REL1_OUT+ Relay 1 switching contact (configurable as NO or NC) REL1_OUT- Relay 1 switching contact REL2_OUT+ Relay 2 switching contact (configurable as NO or NC) REL2_OUT- Relay 2 switching contact REL3_OUT+...
Page 208
Mounting and installation of the compact control panels RT interface [NL] 5.27.2.2 X2 switching contacts relays 6…10 Designation Description REL6_OUT+ Relay 6 switching contact (configurable as NO or NC) REL6_OUT- Relay 6 switching contact REL7_OUT+ Relay 7 switching contact (configurable as NO or NC) REL7_OUT- Relay 7 switching contact REL8_OUT+...
Page 209
Mounting and installation of the compact control panels RT interface [NL] 5.27.2.3 X3 relay 11 + 12 switching contacts Designation Description REL12_OUT+ Relay 12 switching contact (configurable as NO or NC) REL12_OUT- Relay 12 switching contact REL11_OUT+ Relay 11 switching contact (configurable as NO or NC) REL11_OUT- Relay 11 switching contact NO = Normally open...
Page 210
Mounting and installation of the compact control panels RT interface [NL] 5.27.2.6 X6 relay coils 11…14 Designation Description REL11_IN- Relay coil 11, active low REL12_IN- Relay coil 12, active low REL13_IN- Relay coil 13, active low REL14_IN- Relay coil 14, active low Admissible cable cross-section: 0.14…1.5 mm²...
Page 211
Mounting and installation of the compact control panels RT interface [NL] 5.27.2.9 Connection of cable tree to periphery board RT interface Cable tree Periphery board Periphery board 4 loops 2 loops Designation Cable color Signal Designation Designation X4-6 20V- White-green Supply (+) X8-7 VSYS_01 X8-5...
Mounting and installation of the compact control panels RT interface [CH] 5.28 RT interface [CH] 5.28.1 Installation The RT interface FCI2006-C1 [CH] is delivered as a complete set incl. connection cables. The RT interface is already inserted onto the mounting plate in the card cage.
Mounting and installation of the compact control panels RT interface [CH] 1. Screw the round spacer (7) onto the rear panel to right of the periphery board. 2. Screw the two spacers (4) onto the rear panel to the left of the periphery board. 3.
Page 214
Mounting and installation of the compact control panels RT interface [CH] Description Relay 3 switching contact (configurable as NO or NC) Relay 3 switching contact Relay 4 switching contact (configurable as NO or NC) Relay 4 switching contact H1-1 H1-2 H2-1 H2-2 214 | 354...
Page 215
Mounting and installation of the compact control panels RT interface [CH] 5.28.2.2 Connection of cable tree to periphery board RT interface Cable tree 4 loop periphery board 2 loops periphery board Designation Cable color Cable no. Designation Designation Relay 1 Black X8-1 I/O1...
Mounting and installation of the compact control panels Cable kit (communication) 5.29 Cable kit (communication) The cable kit (communication) FCA2014-A1 is used as an intermediate piece for wiring the external lines to the modules on the operating unit. The connecting cables supplied are fully assembled and have a length of 1110 mm.
Mounting and installation of the compact control panels Insert license key 5.30 Insert license key The license key is inserted in the designated holder on the rear of the operating unit. Figure 116: Using the license key on the operating unit with PMI & mainboard FCM2027 Figure 117: Using the license key on the operating unit with PMI &...
Mounting and installation of the compact control panels 19" mounting kit 5.31 19" mounting kit The 19" mounting kit FHA2016-A1 serves as a retainer for installing a station into a 19" rack or into a 19" cabinet. To fix a station, the two retainers enclosed with the kit must be mounted.
Page 219
Mounting and installation of the compact control panels 19" mounting kit 1. Screw the 19" crossbars to the housing bracket. Consider the installation depth of the station. 2. Secure 19" retainers to 19" rack or in 19" cabinet. Consider the mounting height of the station.
Mounting and installation of the compact control panels FM blind 5.32 FM blind The FM blind is required to achieve a level covering of the station in the event of recess mounting. There is one FM blind each for the 1HU and 2HU housing heights: ●...
Page 221
Mounting and installation of the compact control panels FM blind Plastic stopper Ø 12 mm 4 hexagon fixing screws M5 x 10 mm for recess-mounted cover cap FM blind (2 HU) 2 fixing screws used for operating add-on (only with Comfort housing) Operating add-on (only with Comfort housing) Rear panel fixation Rear panel...
Page 222
Mounting and installation of the compact control panels FM blind Recess sizes (W x H x D) ● Housing (Eco) 456 x 424 x 97.5 mm ● Housing (Standard) 456 x 424 x 177.5 mm ● Housing (Large Extension) 456 x 424 x 277.5 mm ●...
Mounting and installation of the compact control panels Batteries 5.33 Batteries Guidelines WARNING Switching batteries in parallel Risk of explosion and fire ● Never connect batteries in parallel! ● If you need more power, you must use batteries with a higher capacity. ●...
Mounting and installation of the compact control panels Operating add-on with 20 zones EVAC-NL [NL] 5.34 Operating add-on with 20 zones EVAC-NL [NL] X400 X401 X402 X400 X402 X400 Figure 121: Example: Installation of the operating add-on with 20 zones EVAC-NL Operating add-on FCM2008-N1 [NL] EVAC-NL operation FTO2007 (slave) EVAC-NL operation FTO2007 (master)
Page 225
Mounting and installation of the compact control panels Operating add-on with 20 zones EVAC-NL [NL] Figure 122: Detail view of the hinge of the operating add-on Cut-out section on the rear panel for the hinge Hinge Screw for securing the hinge 1.
Mounting and installation of the compact control panels Operating add-on with 20 zones EVAC-NL [NL] 5.34.1 Adjustment elements The EVAC-NL indicator is configured with the switch S20. Setting for one or the first EVAC-NL Switch S20 Meaning Master Syn (Empty) Device address 1 Device address 2 Device address 3...
Page 227
Mounting and installation of the compact control panels Operating add-on with 20 zones EVAC-NL [NL] Setting for the second and/or any subsequent EVAC-NL indicator Switch S20 Meaning Master Syn (Empty) Device address 1 Device address 2 Device address 3 Device address 4 Device address 5 Mimic display outputs are actuated and polled (LED, keys and key switch)
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35 Remote EVAC-NL and EVAC-NL mimic display driver 5.35.1 Remote 20-zone EVAC-NL indicator X402 X400 X402 X400 Figure 123: Example of remote mounting of the 20-zone EVAC-NL indicator in an Eco housing EVAC-NL connector board FTI2002-N1 Eco housing (example) Power supply (70 W) (example)
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 1. Mount the operating add-on FCM2008-N1 (5) on the Eco housing (2) or on any housing. 2. If the power supply is integrated, install power supply (3) in the Eco housing (2).
Page 230
Front plate, LED indicators and operation keys for the mimic display panel ● Any DC 24 V power supply or power supply (70 W) FP2015-A1 ● Molex 87586-3493 spring strips (Siemens no. A5Q 00005805) for mimic display connections ● 34 pin x 1 m ribbon cable for mimic display connections ●...
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.3 Pin assignments The EVAC-NL connector board FTI2002-N1 is used as an interface from the EVAC-NL operating unit FTO2007-N1 to the RS485 card in the control panel. Vext.
Page 232
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver In the EVAC mimic display FT2003-N1, the EVAC-NL connector board FTI2002-N1 is supplied together with the EVAC-NL operating unit FTO2007-N1. Vext. FT2003 X2/X3 FTI2002 FTO2007 Vsys RS485 FC20xx...
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.4 Cable length and cable resistance If using a remote EVAC-NL indicator and the EVAC mimic display driver, the length of the power supply cable is limited if the component is supplied internally via the periphery board.
Page 234
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver Example of using the diagram Two remote EVAC-NL indicators, one with 20 zones, the other with 30 zones, are supplied by the periphery board of the same ↑ station. Remote (mimic) EVAC, 20 zones Remote (mimic) EVAC, 30 zones mimic display driver...
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.5 Indicators Indication and operating elements for EVAC-NL operating unit FTO2007-N1 In the case of the EVAC mimic display driver, all display and operating elements are wired to the mimic display panel via three 34-pin ribbon cables.
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.6 Connection FTI2002-N1 See also 2 Power supply (70 W) [➙ 94] 2 RS232 / RS485 module [➙ 185] 5.35.6.1 X1 supply Designation Description VSYS– Supply input from the power supply (–) VSYS–...
Page 237
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.6.2 X2 LED mimic display Connection for LED Master description Slave description 1, 2 H405 (green) Selection zone 5 Selection zone 5 3, 4 H409 (green) Selection zone 9 Selection zone 9 5, 6...
Page 238
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver H405 'Selection zone 5' 'Selection zone 9' H409 'Selection zone 6' H406 'Selection zone 10' H410 H407 'Selection zone 7' H417 'Fault/Isolation zone 7' H416 'Alarm zone 8' H415 'Fault/Isolation zone 8'...
Page 239
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.6.3 X3 LED mimic display LED connection Master description Slave description 1, 2 H422 (red) Alarm zone 5 Alarm zone 5 3, 4 H426 (red) Alarm zone 3 Alarm zone 3 5, 6...
Page 240
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver H422 'Alarm zone 5' 'Alarm zone 3' H426 'Fault/Isolation zone 4' H423 'Fault/Isolation zone 2' H427 H424 'Alarm zone 4' H434 'Totaal Alarm' H433 'Bedrijf' H432 'Uitgeschakeld' H431...
Page 241
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.6.4 X5 mimic display operation LED connection Master description Slave description 1, 2 Selection zone 1 Selection zone 1 3, 4 Selection zone 7 Selection zone 7 5, 6 Totaal alarm 7, 8...
Page 242
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 'Selection zone 1' Selection zone 7 Totaal Alarm 'IN/UIT' 'Selection zone 2' Selection zone 8 'Zoemer uit' 'LED TEST' 'Selection zone 3' Selection zone 9 'Start' Selection zone 5 Selection zone 4...
Mounting and installation of the compact control panels Remote EVAC-NL and EVAC-NL mimic display driver 5.35.7 Connection FTO2007-N1 5.35.7.1 Adjustment elements The EVAC-NL indicator is configured with the switch S20. Setting for one or the first EVAC-NL Switch S20 Meaning Master Syn (Empty) Device address 1 Device address 2...
Mounting and installation of the compact control panels Door contact kit [DE] 5.36 Door contact kit [DE] 5.36.1 Installation The door contact kit FCA2009-A1 is needed for a class 3 key depot [DE] and must not be used for other applications. The door contact is fitted on the housing such that it is triggered when the cover cap is removed.
Mounting and installation of the compact control panels Door contact kit [DE] 5.36.2 Pin assignments Inputs and outputs which are not used do not require termination. 5.36.2.1 X6 intrusion detection system / local alarm / identification lamp Designation Description Ke Leuchte + Identification lamp (+) Ke Leuchte - Identification lamp (-)
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37 Ethernet switch FN2008 and safety module FN2009 The installation description for these modules for extended networking relates to the following modules, which are identical in construction: ●...
Page 247
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 View and installation of mounting kit FHA2029 Figure 131: Mounting kit FHA2029-A1 for installation on the DIN rail 2 fixing screws for the bottom DIN rail Bottom DIN rail Angle plate for the Ethernet switch Retaining bracket for lateral fixing...
Page 248
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.1.1 View of installation in housing (Eco) Figure 132: Installation of mounting kit in the housing (Eco) 2 screws each for DIN rails Bottom DIN rail Lugs for the housing recesses (top and bottom lug) Angle plate 2 screw holes for top DIN rail...
Page 249
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.1.2 View of installation in housing (Standard) Figure 133: Installation of mounting kit in the housing (Standard) 2 screws each for DIN rails Bottom DIN rail Angle plate Lug for the housing recesses (top and bottom lug) 2 screw holes for top DIN rail...
Page 250
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.1.3 View of installation in housing (Comfort) Figure 134: Installation of mounting kit FHA2029-A1 in the housing (Comfort) 2 screws for each DIN rail Bottom DIN rail Angle plate 3 screws for fixing bracket 2 screw holes for top DIN rail...
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.2 Installing the modules The process of installation using the mounting kit is identical for all housing variants and applies to the following modules: ● Ethernet switch (MM) FN2008-A1 ●...
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.3 Wiring of FN2008 with fire terminal FC20xx FT2040 FDnet LINE PMI & Mainboard FCnet/ Ethernet Figure 136: Wiring the FN2008-A1 with I/O module in a separate empty housing with the fire terminal 252 | 354 Building Technologies 008851_s_en_--...
Page 253
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 If cabling is being carried out using multiple PMI & mainboards and the FN2008, a loop can be created accidentally. Please observe the following information. NOTICE Loop with Ethernet cable Impairment of system function...
Page 254
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 Wiring table The wiring table below summarizes the plug assignments from the corresponding product data. Connection from Connector Designation Connector Designation FN2008-A1 Supply+ input Fire terminal board X5 1/3 Vsys+ supply output Supply- input Vsys-- supply output...
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.4 Connecting the Ethernet switch 5.37.4.1 Connecting optical Ethernet Wiring a loop network with four network nodes To set up a redundant loop topology with the Ethernet switch (MM) FN2008-A1, both free ends of the optical Ethernet must be joined to form a loop.
Page 256
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 Ethernet connection to PMI & mainboard Optical Ethernet (loop network) P1…P4 Electrical Ethernet ports P5, P6 Optical Ethernet ports Optical receiver channel Optical transmission channel Wiring WARNING Heavily concentrated light...
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.4.3 Connector strip for detector contact The detector contact is a potential-free relay contact which can be used to report error states by interrupting contact. The following errors can be signaled by the detector contact: ●...
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 5.37.6 Modifications to the modules for class B For the 'Ethernet switch (MM)' and 'Security module (firewall)' modules, the following modifications are required to the wiring to reduce fault transmission from limit value class A to class B: ●...
Page 259
Mounting and installation of the compact control panels Ethernet switch FN2008 and safety module FN2009 Station or empty housing FN2009-A1 Ethernet connection, internal FN2009-A1 Ethernet connection, external Supply connection Ethernet connections switch FN2008-A1 Ferrite core for LAN cable Ferrite core for supply cable Mounting 1.
Mounting and installation of the compact control panels Installation checklist 5.38 Installation checklist The following list serves as a checklist or task list for the installation personnel. It includes all components available as options. It can be copied and handed out to the installation personnel with the installation instructions.
Page 261
Mounting and installation of the compact control panels Installation checklist Position Type Component/task Comment Complete FTO2001-A1 Install event printer An RS232 module must also be fitted to slot 1 FTO2005-A1 Install a key switch (Kaba) – – Install a Redux module Only for Germany [DE] FDCIO224...
Mounting and installation FC2080 Mounting procedure 6 Mounting and installation FC2080 6.1 Mounting procedure The following mounting processes are described in the following chapters: ● Assembling the housing (19", pedestal cabinet) FH2080-AA ● Installing the carrier components ● Installing all other components Prerequisites ●...
Page 263
(EN 54-2 specification). The installation number (No.:) and the date of commissioning (Date:) must be completed upon commissioning. The installation plate is placed together with the processor unit. Siemens Switzerland Ltd Fire Safety & Security Products CH-6301 Zug 115V / 230V 50...60Hz...
Mounting and installation FC2080 Processor unit (19", FC2080) 6.2 Processor unit (19", FC2080) NOTICE Damage to hardware ● Remove the plug-in cards from the card cage first of all before installing the processor unit (19", FC2080). The following accessories are delivered along with the processor unit: ●...
Mounting and installation FC2080 Processor unit (19", FC2080) 6.2.1 Installation The processor unit (19", FC2080) FCC2002-A1 forms part of the FC2080's basic setup and is installed in the top of the cabinet. Figure 141: Installing the processor unit (19", FC2080) Mounting holes in rear frame Mounting holes in the processor unit (height distance 266.7 mm) 4 fixing screws M6 x 12 with cage nuts...
Mounting and installation FC2080 Processor unit (19", FC2080) 6.2.2 View of card cage (CPU) FCC2003-A1 X52 X51 X42 X41 X13 X14 X5001 X5000 Figure 142: Printed circuit board view of card cage (CPU) FCC2003-A1 Element Des. Function Slots Connector strip for plugging in the first ↑ CPU card Connector strip for plugging in the second CPU card (redundant CPU card) Connector strip for plugging in the communication card...
Page 267
Mounting and installation FC2080 Processor unit (19", FC2080) Element Des. Function Connection terminals Connector terminal for system supply 'SDL1', connection terminal for network module (SAFEDLINK, CC) of the first CPU card 'SDL2', connection terminal for network module (SAFEDLINK, CC): ● Degraded mode module on the communication card with Single CPU operation ●...
Mounting and installation FC2080 Processor unit (19", FC2080) 6.2.3 Pin assignments 6.2.3.1 X11/X12 connection terminals for SDL1/SDL2 The ↑ FCnet is connected to the following connection terminals: ● X11 'SDL1'. FCnet connection for network module (SAFEDLINK, CC) of the ↑ CPU card (FC2080) ●...
Page 269
Mounting and installation FC2080 Processor unit (19", FC2080) FCnet FCnet FC2080 FCC2003 FCM20xx FN2010 FN2001 FN2010 Figure 144: ↑ FCnet networking of FG2020 with optional operating unit 269 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
Page 270
Mounting and installation FC2080 Processor unit (19", FC2080) 6.2.3.2 X10 connector terminal for supply Designation Description #BATT Battery signal monitoring (normally open) COMMON GND for #BATT (normally open) #MAINS Signal monitoring power supply system COMMON GND for #MAINS 3SRC+ source (DC 7…30 V) [FR] 3SRC- source (0 V) [FR] VSYS+...
Mounting and installation FC2080 Assembling the carrier (19", card cage) 6.3 Assembling the carrier (19", card cage) The carrier (19" card cage) FHA2023-A1 is supplied with two installed cable ducts but no card cage. Enclosed accessories ● 2 ribbon cables, 24-pin, 750 mm long ●...
Mounting and installation FC2080 Assembling the carrier (19", card cage) 6.3.1 Installing the card cage (5 slots) on the carrier (19", card cage) The carrier (19", card cage) FHA2023-A1 is supplied without a card cage (5 slots) FCA2008-A1. A maximum of two card cages (5 slots) can be installed. Figure 145: Installing the card cage (5 slots) on the carrier (19", card cage) Top cable duct (shown removed) Card cage (5 slots)
Mounting and installation FC2080 Assembling the carrier (19", card cage) 6.3.2 Installing DIN rails on the carrier (19", card cage) The carrier (19", card cage) FHA2023-A1 is supplied with two 180 mm long DIN rails as accessories. These DIN rails can be used to install devices when e.g. only one card cage (5 slots) FCA2008-A1 is installed.
Mounting and installation FC2080 Installing the carrier (19", card cage) 6.4 Installing the carrier (19", card cage) 6.4.1 Installation The carrier (19", card cage) FHA2023-A1 with the installed card cages (5 slots) or the DIN rails is an extension for additional module bus cards and I/O cards and also serves as a carrier for small modules or relays.
Mounting and installation FC2080 Installing the carrier (19", card cage) Element Des. Function Connection terminals System supply connection Connection terminals for module bus card 1 Connection terminals for module bus card 1 Connection terminals for module bus card 2 Connection terminals for module bus card 2 Connection terminals for module bus card 3 Connection terminals for module bus card 3 Connection terminals for module bus card 4...
Page 277
Mounting and installation FC2080 Installing the carrier (19", card cage) 6.4.3.2 X11…X52 connection terminals for the module bus card The module bus card determines the PIN assignment of the four connectors. You will find the pin assignments in the description of the corresponding module card. The assignment of the connector is: ●...
Mounting and installation FC2080 Installing the carrier (19", option) 6.5 Installing the carrier (19", option) The carrier (19", option) FHA2024-A1 is intended for the installation of smaller modules and relays. To this end, it is equipped with two DIN rails that are fitted one above the other.
Mounting and installation FC2080 Installing the battery tray (19") 6.6 Installing the battery tray (19") The battery tray (19") FHA2021-A1 contains two batteries and serves as leakage protection and a holder for fixing batteries with tension belts. The battery tray (19") is supplied with three tension belts for fixing the batteries.
Page 280
Mounting and installation FC2080 Installing the battery tray (19") 8 threaded screws M6 x 12 for securing the crossbeam Threaded holes for securing the compartment 2 crossbeams for the battery tray Lateral crossbars with mounting holes 1. Install the battery tray (1) on the two crossbeams (7) with four countersunk screws (3).
Mounting and installation FC2080 Installing the switch and socket on the carrier (19", power supply) 6.7 Installing the switch and socket on the carrier (19", power supply) The carrier (19", power supply) FHA2022-A1 is supplied without a main switch and socket.
Mounting and installation FC2080 Installing the power supply kit (150 W, B) 6.8 Installing the power supply kit (150 W, B) 6.8.1 Installation The carrier (19", power supply) FHA2022-A1 is supplied with two power supplies (150 W) connected in parallel. For more power, a third power supply can be installed with the power supply kit (150 W, B) FP2005-A1.
Page 283
Mounting and installation FC2080 Installing the power supply kit (150 W, B) Carrier (19", power supply) Clamps for securing to the DIN rail Mounting slots for right-hand retaining bracket Additional third power supply (150 W), slave Power supply (150 W), slave Power supply (150 W), master Primary terminals with main switch Clamping screw M3 x 6 for third power supply (150 W)
Mounting and installation FC2080 Installing the power supply kit (150 W, B) ● In order to avoid operating temperature differences, all three power supply units must be mounted next to each other in the same housing. ● The batteries must be connected to the master power supply. ●...
Page 286
Mounting and installation FC2080 Installing the power supply kit (150 W, B) 1...6 K1K2 1 2 3 4 5 6 >Master Slave 2 Master Slave Slave 1 Master Slave Master Figure 155: View of cable tree wiring for the third additional power supply Slave 1 Second existing power supply (150 W) Slave 2...
Page 287
Mounting and installation FC2080 Installing the power supply kit (150 W, B) 24 V Vsys +24 V terminal block Vsys 0 V terminal block Circuit breaker for charging current (20 A) Monitoring relay 1 Monitoring relay 1 Wiring table for signal and system voltage connections of the 3rd power supply (slave 2) Connector Wire up according to...
Mounting and installation FC2080 Installing the carrier (19", power supply) 6.9 Installing the carrier (19", power supply) The carrier (19", power supply) FHA2022-A1 is installed on the side of the cabinet. The installation position can be determined depending on the arrangement of the other components and the battery tray.
Page 289
Mounting and installation FC2080 Installing the carrier (19", power supply) Figure 156: Installing the carrier (19", power supply) with details of the mounting points Carrier (19", power supply) Crossbars on the sides of the housing Main switch for mains supply cable 4 fixing screws with nuts Mounting points for top carrier Mounting points for bottom carrier...
Page 290
Mounting and installation FC2080 Installing the carrier (19", power supply) Installation positions for two carriers (19", power supply) When installing two carriers (19", power supply), the carriers should be installed as high as possible to keep sufficient space for the battery trays. Top mounting point for first carrier Bottom mounting point for first carrier Top mounting point for second carrier...
Mounting and installation FC2080 Installing the carrier (19", power supply) 6.9.1 Wiring up the mains voltage The primary wiring supplies and outlets must be secured with cable ties. L1 L1 N N L2 L2 L PE N Figure 157: Cable guide of the mains supply cable on carrier (19", power supply) Integrated power supply (150 W), PS1…PS3 Mains cable duct Install the main switch, only for the first carrier (19", power supply)
Page 292
Mounting and installation FC2080 Installing the carrier (19", power supply) Wiring of the mains cable on the bottom terminal block PSU1 X1/PS1 X1/PS2 X1/PS3 N N L1 L1 PE PE PE N N N N N L2 L2 L PE N PSU2 Mains connection Figure 158: Wiring diagram of the complete bottom terminal block on carrier (19", power supply)
Page 293
Mounting and installation FC2080 Installing the carrier (19", power supply) Connection From Mains supply cable External conductor (L) Main switch L2 (bottom) Neutral conductor (N) Main switch N (bottom) Protective conductor (PE) Terminal PE (bottom) Earth connection Terminal PE (top) Ground connection terminal Primary terminals (L, N)
Mounting and installation FC2080 Installing the carrier (19", power supply) 6.9.2 Installing the temperature sensor Figure 159: Installing the temperature sensor for batteries Carrier (19", power supply) Mounting location of temperature sensor for second, top battery kit Second, top battery kit Mounting location of temperature sensor for first, bottom battery kit First, bottom battery kit 294 | 354...
Page 295
Mounting and installation FC2080 Installing the carrier (19", power supply) Nut M3 Washer M3 Spacer sleeve M3 2-pin luster terminal 10 Screw M3 1. Position the luster terminal (9) as close as possible to the top of the batteries (3) or (5) on the crossbar according to the diagram. 2.
Mounting and installation FC2080 Wiring up the system supply and module bus 6.10 Wiring up the system supply and module bus The following guidelines must be observed when wiring the module bus and system supply. Guidelines WARNING Switching batteries in parallel Risk of explosion and fire ●...
Page 297
Mounting and installation FC2080 Wiring up the system supply and module bus Vsys Card cage (CPU) Card cage VBatt FCC2003 (5 slots) FCA2008 1...6 K1K2 Card cage Card cage (5 slots) (5 slots) FCA2008 FCA2008 PSU1 Vsys VBatt Card cage Card cage (5 slots) (5 slots)
Page 298
Mounting and installation FC2080 Wiring up the system supply and module bus VBatt Battery supply +24 V/0 V 1…6 Terminal block for signal connections 15 A circuit breaker for +24 V battery supply Monitoring signal optocoupler #BATT Monitoring signal optocoupler #MAINS X5000 Module bus output 1, card cage (CPU) X5001...
Page 299
Mounting and installation FC2080 Wiring up the system supply and module bus Wiring diagram with one carrier (19", power supply) FCC2002-A1 Control unit (19", FC2080) FCC2003-A1 FCA2008-A1 X500 X501 X5000 X5001 Cardcage Cardcage 5...7 2...4 FCA2008-A1 1 VSYS+ VSYS+ VSYS+ VSYS- VSYS- Battery pack 1...
Page 300
Mounting and installation FC2080 Wiring up the system supply and module bus Wiring diagram with two carriers (19", power supply) FCC2002-A1 Control unit (19", FC2080) FCC2003-A1 FCA2008-A1 X501 X5000 X5001 X500 Cardcage Cardcage 5...7 2...4 FCA2008-A1 1 VSYS+ VSYS+ VSYS+ VSYS- VSYS- VSYS-...
Page 301
Mounting and installation FC2080 Wiring up the system supply and module bus Wiring monitoring signals The following diagrams and pin assignments show the wiring of the monitoring signals from the power supplies to the optocouplers. FCC2003-A1 #BATT COMMON #MAINS COMMON 3SRC+ 3SRC- VSYS+...
Page 302
Mounting and installation FC2080 Wiring up the system supply and module bus FCC2003-A1 #BATT COMMON #MAINS COMMON 3SRC+ 3SRC- VSYS+ 11 14 11 14 VSYS+ VSYS- A1 A2 A1 A2 VSYS- PSU1 11 14 11 14 A1 A2 A1 A2 PSU2 Figure 164: Wiring of monitoring signals with two carriers (19", power supply) 302 | 354...
Page 303
Mounting and installation FC2080 Wiring up the system supply and module bus Pin assignment for two carriers (19", power supply): Signal From optocoupler To optocoupler To terminal X10 Battery PSU2/K1-11 X10-1 (#BATT) PSU2/K1-14 PSU1/K1-11 PSU1/K1-14 X10-2 (COM) Mains PSU2/K2-11 X10-3 (#MAINS) PSU2/K2-14 PSU1/K2-11 PSU1/K2-14...
Mounting and installation FC2080 Installing the CPU card and communication card 6.11 Installing the CPU card and communication card 6.11.1 Installation in card cage Installing the cards Figure 165: Installing the plug-in cards in the processor unit (19", FC2080) Processor unit (19", FC2080) Card cage (5 slots) Card cage (CPU) Connector strip for communication card (FC2080)
Page 305
Mounting and installation FC2080 Installing the CPU card and communication card Figure 166: Arrangement of the plug-in cards in the processor unit (19", FC2080) Processor unit (19", FC2080) CPU card (FC2080) in slot 1 Redundant CPU card (FC2080) in slot 2 Communication card (FC2080) in slot 3 Slot 4 for module bus cards or I/O cards, e.g.
Mounting and installation FC2080 Installing the CPU card and communication card 6.11.2 Switching the network module with dual CPU operation If a second CPU card is installed for redundant CPU operation, the network module must be removed from the communication card and plugged into the second CPU card, before it is installed, as shown.
Mounting and installation FC2080 Installing the CPU card and communication card 6.11.3 Ethernet connection The CPU card and communication card are connected via the Ethernet connections of the corresponding cards. Both the CPU cards and the communication card must be connected to each other to ensure redundancy. When operating with two CPU cards, the network module (SAFEDLINK, CC) must be removed from the communication card and fitted on the CPU card! Wiring with a CPU card...
Mounting and installation FC2080 Insert license key 6.12 Insert license key The license key is inserted in the communication card (FC2080/FG2020) in the holder intended for it. Prerequisites Note the wiring of the Ethernet cable before you remove the card for the installation of the license key.
Mounting and installation FC2080 Installing the operating unit and operating add-on 6.13 Installing the operating unit and operating add-on The fire control panel FC2080 has no integrated operating unit. The operating unit and a maximum of two operating add-ons form a station of their own within the FC2080.
Page 310
Mounting and installation FC2080 Installing the operating unit and operating add-on Figure 171: Installing the required components, taking operating unit FCM2028-A1 as an example Operating unit Flange with threaded holes for securing the module Connector strip X13 for network module Network module (SAFEDLINK) FN2001-A1 with ES ≥...
Page 311
Mounting and installation FC2080 Installing the operating unit and operating add-on Installing operating unit Figure 172: Mounting operating terminal in door, taking operating unit FCM2028-A1 as an example Inside of door Opening for operating unit 4x welded threaded bolts 4x mounting holes in the operating unit 4x fixing screws 1.
Mounting and installation FC2080 Installing the operating unit and operating add-on 6.13.2 Wiring Figure 173: Wiring up the operating unit and the operating add-on Peripheral data bus connection on operating unit for options FCnet connection terminal on network module (SAFEDLINK) Inside of door Operating unit Ribbon cable for peripheral data bus...
Mounting and installation FC2080 Installing the key safe adapter [DE] 6.14 Installing the key safe adapter [DE] The key safe adapter SDA3000 [DE] is used to connect the fire brigade key depot [DE] to the fire control panel FC2080. The following options for controlling the key safe adapter are available and are described using examples for the wiring: ●...
Mounting and installation FC2080 Installing the key safe adapter [DE] Example of installation 1. Prepare the carrier (19", option) (1) for the installation of the key safe adapter (6) by mounting or removing the DIN rails as appropriate. 2. Install the key safe adapter (6) on one of the three positions provided on the carrier (19", option) (1).
Page 315
Mounting and installation FC2080 Installing the key safe adapter [DE] Example of installation 1. Mount the key safe adapter (6) on the carriers of the right-hand side wall (1). 2. Mount an additional DIN rail (3) on the right-hand side wall as shown in the example.
Mounting and installation FC2080 Installing the key safe adapter [DE] 6.14.3 SDA wiring via I/O module and FDnet control Control via the I/O module FDCIO224 with control via the FDnet as an example of in-principle wiring is shown below. Use of FDCIO224 is obligatory for extinguishing applications.
Page 317
Mounting and installation FC2080 Installing the key safe adapter [DE] FCI2007-A1 I/O card (RT) FCL2001-A1 Line card (FDnet/C-NET) FDCIO224 I/O module SDA3000 Key safe adapter SDA3000 [DE] Fire brigade key depot [DE] 317 | 354 008851_s_en_-- Building Technologies Fire Safety 2016-01-27...
Mounting and installation FC2080 Installing the key safe adapter [DE] 6.14.4 SDA wiring via I/O module FDCIO222 In the following example, with control via I/O module FDCIO222, the heating of the key safe adapter is wired so that it is isolated in the event of an alarm or a power failure.
Page 319
Mounting and installation FC2080 Installing the key safe adapter [DE] FDCIO222 I/O module SDA3000 Key safe adapter SDA3000 [DE] Fire brigade key depot [DE] Wiring the FDCIO222 with 1.15 kΩ and 3.01 kΩ resistors applies for monitoring for short-circuits and open circuits. 319 | 354 008851_s_en_-- Building Technologies...
Mounting and installation FC2080 Installing the key safe adapter [DE] 6.14.5 SDA wiring via an I/O card An example of in-principle wiring with control via a (programmable) FCI2008-A1 I/O card is shown below. FCI2008-A1 SD-Sabotage I/O1 UE Aktiv/bestätigt I/O2 Summenalarm I/O3 Heizung I/O4...
Page 321
Mounting and installation FC2080 Installing the key safe adapter [DE] FCI2008-A1 I/O card (programmable) FCL2001-A1 Line card (FDnet/C-NET) Key safe adapter SDA3000 [DE] Fire brigade key depot [DE] The supply and the inputs/outputs must be connected to the same I/O card. 321 | 354 008851_s_en_-- Building Technologies...
Mounting and installation FC2080 Installing the fiber optic cable network module 6.15 Installing the fiber optic cable network module 6.15.1 Installation The identical fiber optic cable network modules FN2006-A1 and FN2007-A1 can be installed on a DIN rail either horizontally or vertically. To do this, the DIN rail clips must be changed from the rear side to the rear face.
Mounting and installation FC2080 Installing an Ethernet switch (MM) FN2008 6.16 Installing an Ethernet switch (MM) FN2008 6.16.1 Installation The Ethernet switch (MM) FN2008-A1 is installed vertically on a DIN rail. The following example shows the installation on the DIN rail on the side wall. Figure 180: Example of installation of the Ethernet switch in the FC2080 Ethernet switch (MM) Additional DIN rail with terminal block (if required) and locking clamps...
Mounting and installation FC2080 Installing an Ethernet switch (modular) FN2012 6.17 Installing an Ethernet switch (modular) FN2012 You will find information on the wiring and pin assignment in 'Mounting and installation of the compact control panels'. See also 2 Installing an Ethernet switch (modular) FN2012 [➙ 142] 6.17.1 FHA2029 in the housing (19", pedestal housing) Figure 181: Installing the large mounting bracket in the 19"...
Mounting and installation FC2080 Installing an Ethernet switch (modular) FN2012 Lateral support rail in the 19" pedestal housing Mounting holes in lateral support rail Large mounting bracket from FHA2029 4x mounting holes in mounting bracket 4x fixing screws for mounting bracket U-rail installed Retaining bracket installed 1.
Mounting and installation FC2080 Installing the battery kit (9 V) [FR] 6.18 Installing the battery kit (9 V) [FR] 6.18.1 Installation The battery kit 9 V FCA2010-F1 [FR] is a holder for a 9 V monobloc battery and is required in France for maintaining emergency supply in the case of battery failure. Figure 184: Installing the 9 V battery kit in the FC2080 Additional DIN rail with terminal block (if required) and locking clamps Carrier on the right-hand side wall...
Mounting and installation FC2080 Install batteries 6.19 Install batteries The batteries must be secured with the tensioning set belts supplied. The tensioning belts for fixing the batteries must not be twisted. The clamping device must not be on an edge. Install the edge protector provided. Figure 185: FC2080, installing the batteries and fixing them with tensioning belts Clamping device (tensioning set) 3x tensioning belts...
Page 328
Mounting and installation FC2080 Install batteries 1. Place the batteries (6) as shown in the installed battery tray (4). 2. Loop the belts of the tensioning set (2) as shown under the battery tray (4) and around the batteries (6). One belt should be placed along each battery and one across both batteries.
Mounting and installation of fire terminal (Touch) Setup of fire terminal (Touch) FT2080 7 Mounting and installation of fire terminal (Touch) 7.1 Setup of fire terminal (Touch) FT2080 Figure 186: Rear panel fire terminal (Touch) FT2080 Support plate Front indicator (Touch) FTO2010 PMI &...
Page 330
Mounting and installation of fire terminal (Touch) Setup of fire terminal (Touch) FT2080 Arrangement of components Figure 187: Components on the fire terminal (Touch) FT2080, without cover cap Front indicator (Touch) FTO2010 Main network module (SAFEDLINK) on X13, optional License key, optional Slot 1 [SER_OPT1] for the first serial module at X14, optional Slot 2 [SER_OPT2] for the second serial module at X19, optional Degraded mode network module (SAFEDLINK) on X12, optional...
Mounting and installation of fire terminal (Touch) Installation in 19" pedestal housing of the FC2080 7.2 Installation in 19" pedestal housing of the FC2080 The installation instructions described below apply to all operating units. Before an operating terminal is installed, the following components must first be mounted on the operating unit.
Page 332
Mounting and installation of fire terminal (Touch) Installation in 19" pedestal housing of the FC2080 2x fixing screw PMI & mainboard FCM2027 Adapter for power supply (including ribbon cable) Connector strip X3 peripheral data bus connection 1. Plug the network module (SAFEDLINK) (4) into connector X13 (3) of the operating unit (1).
Page 333
Mounting and installation of fire terminal (Touch) Installation in 19" pedestal housing of the FC2080 Wiring the fire terminal (Touch) Figure 190: Wiring the fire terminal (Touch) with FC2080 Ribbon cable for FC2080 system supply to card cage (CPU) X30 FCnet connection to card cage (CPU) X11/X12 X3 connection to network module (SAFEDLINK) to PMI &...
Mounting and installation of fire terminal (Touch) Installation in housing (standard) 7.3 Installation in housing (standard) Figure 192: Installation of fire terminal in the housing (standard) FH2002 Mains connection terminals Power supply unit (70 W) FP2015 Rear panel (standard) Fire terminal board FTI2001 Wiring FCnet/SAFEDLINK Network module (SAFEDLINK) FN2001 Fire terminal (Touch) FT2080...
Mounting and installation of fire terminal (Touch) Installation in rear panel (FT2080) FHA2039 7.4 Installation in rear panel (FT2080) FHA2039 The rear panel (FT2080) can be used for installation in a desk or installation in a third-party housing. Installing the rear panel (FT2080) in a third-party housing guarantees the required EMC protection.
Page 336
Mounting and installation of fire terminal (Touch) Installation in rear panel (FT2080) FHA2039 Installing fire terminal board FTI2001 Figure 194: Installing the fire terminal board in the rear cover (FT2080) Rear panel (FT2080) FHA2039 Fire terminal board FTI2001 4x fixing screws 4x mounting holes Threaded press-in sleeves in rear cover (FT2080) 1.
Page 337
Mounting and installation of fire terminal (Touch) Installation in rear panel (FT2080) FHA2039 Wiring the fire terminal (Touch) When installing in a desktop that is thicker than 33 mm, the cables must be routed through the rectangular openings of the rear panel (FT2080), and not through the round cable breakthroughs.
Page 338
Mounting and installation of fire terminal (Touch) Installation in rear panel (FT2080) FHA2039 1. Wire up the flat cable from the fire terminal board X3 to the PMI & mainboard 2. Wire up the prefabricated cable of the supply from the EMC filter to the fire terminal board X7.
Page 339
Mounting and installation of fire terminal (Touch) Installation in rear panel (FT2080) FHA2039 1. Position the wired-up fire terminal (Touch) (1) on the rear panel (7) as shown. 2. Screw the four fixing screws (2) through the holes (3) to secure the fire terminal (Touch) (1) into the threaded holes (5) in the rear panel.
Mounting and installation of fire terminal (Touch) Installation in desktop housing (FT2080) FHA2040 7.5 Installation in desktop housing (FT2080) FHA2040 Figure 198: View of desktop housing (FT2080) Top of desktop housing Tilting bracket for top of housing Base of desktop housing M4x10 pan head screw (scope of delivery) Clamping bracket for ground cable (scope of delivery) 250 V EMC filter, 3 A with plug-in contacts (mounted)
Page 341
Mounting and installation of fire terminal (Touch) Installation in desktop housing (FT2080) FHA2040 1. Remove the top of housing (1) by pushing the two tilting brackets (2) on the left and right inwards until you can lift off the top of housing. 2.
Page 342
Mounting and installation of fire terminal (Touch) Installation in desktop housing (FT2080) FHA2040 Installing fire terminal (Touch) FT2080 Figure 200: Mounting in top of housing Tilting brackets on left and right for fixing the top of the housing 2x fixing screws for tilting brackets and fire terminal 2x fixing screws for fire terminal Fire terminal (Touch) FT2080 Top of desktop housing (FT2080) FHA2040...
Page 343
Mounting and installation of fire terminal (Touch) Installation in desktop housing (FT2080) FHA2040 Assembly of desktop housing (FT2080) Figure 201: Assembly of desktop housing Fire terminal (Touch) FT2080 Top of desktop housing (FT2080) FHA2040 Tilting brackets on left and right for fixing the top of the housing Guide cams on left and right for tilting brackets 2x threaded holes for fixing the top of the housing Base of desktop housing...
Page 344
Mounting and installation of fire terminal (Touch) Installation in desktop housing (FT2080) FHA2040 Figure 202: Securing the top of the desktop housing Securing cap (scope of delivery) Opening for fixing screw Top of the desktop housing (Touch) Fixing screw with securing device 1.
Page 345
Mounting and installation of fire terminal (Touch) Installation in desktop housing (FT2080) FHA2040 Fire terminal wiring Figure 203: Wiring view of the fire terminal in the desktop housing Fire terminal (Touch) FT2080 Network module (FCnet/SAFEDLINK) FN2001 Fire terminal board FTI2001 Prefabricated cable for supply connection to X7 fire terminal board FCnet connection cable EMC filter...
Replacing components 8 Replacing components The components are dismantled in reverse sequence of installation. To replace components if repairs are necessary proceed as follows: ● Take the station out of operation. ● WARNING! Mortal danger due to electric shock. Before working on the station check that the mains supply cable is disconnected from the power supply.
Concluding work Insert printing paper 9 Concluding work 9.1 Insert printing paper The printer can also be fitted the other way round, i.e. different from the position shown below. Opening the printer Push the clips slightly down and open the printer as shown in the figure. Figure 204: Opening the printer 347 | 354 008851_s_en_--...
Page 348
Concluding work Insert printing paper Replacing the paper roll 1. Remove the reel of the old paper roll. 2. Insert the new paper roll as shown in the figure below. Please make sure that the side that will be unwound is at the back of the drum, corresponding to the dashed line in the figure below.
Page 349
Concluding work Insert printing paper Closing printer 1. Pull some of the paper out of the printer. 2. Hold the paper end upwards. 3. Close the printer by holding the bracket upwards until the clips audibly engage. a The printer is ready. Figure 206: Closing printer 349 | 354 008851_s_en_--...
Page 350
Concluding work Insert printing paper Figure 207: Printer is ready 350 | 354 Building Technologies 008851_s_en_-- Fire Safety 2016-01-27...
This type of wiring allows all detectors to communicate with the control panel even in the event of an open line or short-circuit. Network module (SAFEDLINK) FS20/FS720 network card. Normal operation The fire detection installation is supplied with mains voltage. Normally closed contact Opens a power circuit when activated.
Index Index FTO2001-A1 ..........189 FTO2005-C1 ..........194 Download center URL ..............11 Original language Source language ..........10 FCA2001-A1 ..........185 FCA2002-A1 ..........185 Printer FCA2006-A1 ..........158 Inserting paper..........347 FCA2007-A1 ..........159 FCA2008-A1 ..........159 FCA2009-A1 ..........244 Source language ..........