Views - Siemens 13-xx-ST-SBT Series Product Data

Fire detection system
Table of Contents

Advertisement

35
Communication card (FC2080) FCC2005-A1

Views

35.2
Element
Connector
Module
202
Building Technologies
Fire Safety
NOTICE
If an operating unit is integrated in the FC2080, then the earth fault monitoring of
the system supply must be deactivated on the PMI & mainboard FCM2027 (S 38
to OFF).
Views
5
4
3
2
1
Communication card (FC2080), front and PCB view
Des. Function
1
Port 1, Ethernet connection 10 BASE-T/100 BASE-T
2
Port 2, Ethernet connection 10 BASE-T/100 BASE-T
3
Port 3, Ethernet connection 10 BASE-T/100 BASE-T
4
Port 4, Ethernet connection 10 BASE-T/100 BASE-T
5
Port 5, Ethernet connection 10 BASE-T/100 BASE-T, with earth fault monitoring
X4
Plug-type connection to the card cage
6
Network module (SAFEDLINK, CC) FN2010-A1
7
Holder for the license key
X4
6
7
008837_q_en_--