Issue 01/06
P1582[3]

Smooth time for flux setpoint

CStat:
CUT
P-Group: CONTROL
Sets time constant of PT1 filter to smooth flux setpoint.
Index:
P1582[0] : 1st. Drive data set (DDS)
P1582[1] : 2nd. Drive data set (DDS)
P1582[2] : 3rd. Drive data set (DDS)
r1583

CO: Flux setpoint (smoothed)

P-Group: CONTROL
Displays smoothed flux setpoint in [%] relative to rated motor flux.
P1596[3]

Int. time field weak. controller

CStat:
CUT
P-Group: CONTROL
Sets integral time for field weakening controller.
Index:
P1596[0] : 1st. Drive data set (DDS)
P1596[1] : 2nd. Drive data set (DDS)
P1596[2] : 3rd. Drive data set (DDS)
r1597
CO: Outp. field weak. controller
P-Group: CONTROL
Displays output signal of field weakening controller in [%] relative to rated motor flux.
r1598

CO: Flux setpoint (total)

P-Group: CONTROL
Displays total flux setpoint in [%] relative to the rated motor flux.
P1610[3]
Continuous torque boost (SLVC)
CStat:
CUT
P-Group: CONTROL
Sets the constant torque boost for the low frequency range when sensorless closed-loop vector control is
being used (SLVC). The parameter is entered as a % referred to the rated motor torque (r0333).
For sensorless closed-loop vector control, when the motor model is disabled, an absolute current is
impressed. P1610 represents the maximum load that occurs at a constant setpoint.
i
(P1610, P1611)
sd
r0331
P0346
Index:
P1610[0] : 1st. Drive data set (DDS)
P1610[1] : 2nd. Drive data set (DDS)
P1610[2] : 3rd. Drive data set (DDS)
Caution:
P1610 should always be set at least 10% higher than the maximum steady-state load that occurs.
Note:
-
For P1610 = 0 %, a current setpoint is calculated that corresponds to the no-load case (rated
magnetization current).
-
For P1610 = 100 %, a current setpoint is calculated that corresponds to the rated motor torque.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Active: Immediately
Datatype: Float
Datatype: U16
Active: Immediately
Datatype: Float
Datatype: Float
Datatype: Float
Active: Immediately
i
f
sd
P1755
Parameter Description
Min:
Unit: ms
Def:
QuickComm.: No
Max:
Min:
Unit: %
Def:
Max:
Min:
Unit: ms
Def:
QuickComm.: No
Max:
Min:
Unit: %
Def:
Max:
Min:
Unit: %
Def:
Max:
Min:
Unit: %
Def:
QuickComm.: No
Max:
f(t)
i
(t)
sd
P1610 = P1611 = 0
t
Level
4
3
15
500
Level
-
4
-
-
Level
20
3
50
32001
Level
-
4
-
-
Level
-
3
-
-
Level
0.0
2
50.0
200.0
181