Fixed Frequency Mode - Bit 5; Bi: Fixed Freq. Selection Bit 5 - Siemens MICROMASTER 440 Parameter Manual

0.12 kw - 250 kw
Hide thumbs Also See for MICROMASTER 440:
Table of Contents

Advertisement

Issue 01/06
P1027[3]

Fixed frequency mode - Bit 5

CStat:
CT
P-Group: SETPOINT
direct selection or direct selection + ON for bit 5
Possible Settings:
1
Direct selection
2
Direct selection + ON command
Index:
P1027[0] : 1st. Command data set (CDS)
P1027[1] : 2nd. Command data set (CDS)
P1027[2] : 3rd. Command data set (CDS)
Details:
See parameter P1001 for description of how to use fixed frequencies.
P1028[3]

BI: Fixed freq. selection Bit 5

CStat:
CT
P-Group: COMMANDS
Defines origin of fixed frequency selection.
Index:
P1028[0] : 1st. Command data set (CDS)
P1028[1] : 2nd. Command data set (CDS)
P1028[2] : 3rd. Command data set (CDS)
Dependency:
Accessible only if P0701 - P0706 = 99 (function of digital inputs = BICO).
Details:
See P1020 (fixed frequency selection Bit 0) for most common settings.
MICROMASTER 440
Parameter List
6SE6400-5BB00-0BP0
Datatype: U16
Unit: -
Active: first confirm
QuickComm.: No
Datatype: U32
Unit: -
Active: first confirm
QuickComm.: No
Parameter Description
Level
Min:
1
3
Def:
1
Max:
2
Level
Min:
0:0
3
Def:
722:5
Max:
4000:0
119