The settings necessary for the directional earth fault protection are as follows:
Element
Range
DEFF
DEFFI
0.5 - 5.0 A
(0.10 - 1.00 A
DEFFV
1.7 – 21.0 V
TDEF
0.0 – 10.0 s
DEFR
DEFRI
0.5 - 5.0 A
(0.10 - 1.00 A
DEFRV
1.7 – 21.0 V
TDER
0.0 – 10.0 s
DEF θ
0 - 90°
DEFFEN
OFF/ON
DEFREN
OFF/ON
EFIBT
OFF/NOD/F/R
(*) Current values shown in the parentheses are in the case of 1 A rating. Other current values are in
the case of 5 A rating.
The DEF element is shared with the command protection.
The EFIBT is the scheme switch for directional control selection and if NOD is selected, the
inverse time overcurrent protection executes non-directional operation. If F or R is selected, it
executes forward operation or reverse operation in combination with the DEFF or DEFR. If OFF
is selected, the inverse time overcurrent protection is blocked.
Step
Default
Remarks
Forward looking DEF
0.1 A
1.0 A
Residual current
0.01 A
0.2 A) (*)
0.1 V
2.0 V
Residual voltage
0.1 s
0.0 s
Definite time setting
Reverse looking DEF
0.1 A
1.0 A
Residual current
0.01 A
0.2 A) (*)
0.1 V
2.0 V
Residual voltage
0.1 s
0.0 s
Definite time setting
85°
Characteristic angle
OFF
Forward DEF backup trip enable
OFF
Reverse DEF backup trip enable
NOD
EFI directional control
 82 