Grl100-7**b series. line differential relay
Table of Contents

Advertisement

Reach setting
0.01 - 0.05Ω
(0.1 - 0.2Ω
0.06 - 0.09Ω
(0.3 - 0.4Ω
0.10 - 1.00Ω
(0.5 - 5.0Ω
1.01 - 10.00Ω
(5.1 - 50.0Ω
10.01 - 20.00Ω
(50.1 – 100.0Ω
20.01 - 50.00Ω
(100.1 – 250.0Ω
(*) Values shown in parentheses are in the case of 1A rating.
Other values are in the case of 5A rating.
Set the voltage and current phase relationship as shown below. That is, V a lags Vc by 90°, Vb
= - V a and IT lags V a by θ or θ + 180°. θ is 90° when testing.
V b
Z1S, Z2S, Z3S and PSB
Adjust the magnitude of V a and V b while retaining the conditions above and measure the
voltage V a at which the element operates.
The theoretical operating voltage is obtained by 2IT × ZS when the setting reach is ZS. Check
that the measured voltage is within the above-mentioned error of the theoretical voltage value
when it is expressed with 2V a (= V a − V b ).
Element reach setting (ZS)
Z1S
Z2S
Z3S
Z4S
ZRS
PSBSIN
PSBSOUT
IT
25A
5A)(*)
20A
4A)
10A
2A)
5A
1A)
2.5A
0.5A)
1A
0.2A)
V c
90°
V a
θ
IT
2IT × ZS
IT
 254 
Error
±10%
±7%
±5%
±5%
±5%
±7%
V c
IT
V b
θ + 180°
Z4S
Measured voltage (2V
)
a
6 F 2 S 0 8 5 0
V a