Toshiba GRL100-701B Instruction Manual page 253

Grl100-7**b series. line differential relay
Table of Contents

Advertisement

I out ≤ DIFI2
where, DIFI1 and DIFI2 are setting values.
• Set the charging current compensation DIFIC to zero.
• Press 4 (=Logic circuit) on the "Test" sub-menu screen to display the "Logic circuit" screen.
• Enter a signal number 41 to observe the DIF-A output at monitoring jack A and press the
ENTER key.
• Apply a fixed infeed current to one relay. Apply an outflow current to another relay, change the
magnitude of the current applied and measure the value at which the element operates.
• Repeat the above by changing the magnitude of the infeed current.
• Check that the measured value of the outflow current is within ± 7% of the theoretical values
obtained using the equations mentioned above. (The infeed current is more than 0.5 × In).
6.5.1.2
Residual current differential element DIFG
The residual current differential element is checked on the operating current and percentage
restraining characteristic in the same way as described in Section 6.5.1.1.
The differences from the procedure described in Section 6.5.1.1 are as follows.
• Apply a test current to terminal 7 and 8 instead of 1 and 2.
• Enter a signal number 44 instead of 41 to observe the DIFG element operation at monitoring
jack A.
• Use the settings DIFGI instead of DIFI1.
Element
Signal number
DIFG
44